Instruction manual

14
000AH: C (W/Re5-26) [0 to 2315
]
000BH: Pt100 [–199.9 to 850.0
]
000CH: JPt100 [–199.9 to 500.0
]
000DH: Pt100 [–200 to 850
]
000EH: JPt100 [–200 to 500
]
000FH: K [–320 to 2500
]
0010H: K [–199.9 to 750.0
]
0011H: J [–320 to 1800
]
0012H: R [0 to 3200
]
0013H: S [0 to 3200
]
0014H: B [0 to 3300
]
0015H: E [–320 to 1500
]
0016H: T [–199.9 to 750.0
]
0017H: N [–320 to 2300
]
0018H: PL-
[0 to 2500 ]
0019H: C (W/Re5-26) [0 to 4200
]
001AH: Pt100 [–199.9 to 999.9
]
001BH: JPt100 [–199.9 to 900.0
]
001CH: Pt100 [–300 to 1500
]
001DH: JPt100 [–300 to 900
]
001EH: 4 to 20mA DC[–1999 to 9999]
001FH: 0 to 20mA DC[–1999 to 9999]
0020H: 0 to 1V DC [–1999 to 9999]
0021H: 0 to 5V DC [–1999 to 9999]
0022H: 1 to 5V DC [–1999 to 9999]
0023H: 0 to 10V DC [–1999 to 9999]
20H/50H 03H/06H 0045H: Direct/Reverse action selection 0000H: Heating (Reverse action)
0001H: Cooling (Direct action)
20H/50H 03H/06H 0046H: Not used
20H/50H 03H/06H 0047H: Not used
20H/50H 03H/06H 0048H: Alarm 1 (A1) action
Energized/Deenergized
0000H: Energized
0001H: Deenergized
20H/50H 03H/06H 0049H: Alarm 2 (A2) action
Energized/Deenergized
0000H: Energized
0001H: Deenergized
50H 06H 0070H: Key operation change flag
clearing
0000H: No action
0001H: All clearing
20H 03H 0080H: PV (input value) reading Current PV
20H 03H 0081H: Control output MV
(manipulated variable) reading
Control output MV
20H 03H 0082H: Not used
20H 03H 0083H: Current SV reading Current SV
20H 03H 0084H: Running step remaining time
reading
Remaining time
20H 03H 0085H: Running pattern, step number
reading
16
0
: Pattern number
16
1
: Step number
16
2
: Not used (Always 0)
16
3
: Not used (Always 0)
20H 03H 0086H: Instrument status reading 2
15
to 2
0
0000
0000 0000 0000
2
0
digit: Control output (OUT)
0: OFF 1: ON
(For current output, Not decided)
2
1
digit: Not used (Always 0)
2
2
digit: Alarm 1 (A1) output
0: OFF 1: ON
2
3
digit: Alarm 2 (A2) output
0: OFF 1: ON
2
4
digit: Event output
0: OFF 1: ON
2
5
digit: Not used (Always 0)
2
6
digit: Not used (Always 0)