User Manual
92
Step 5 time
or
Set to 2:00.
Step 5 wait value
or
Set to 0 .
(Many times) or (3 sec)
RUN mode
Standby (program control waiting) mode
Now, selection is complete.
Program control RUN
To perform Program control, press and hold the key for approx. 1 second in Standby (program
control waiting) mode.
Program control starts using the start type selected in [Program control start type].
While Wait function is working, the PV Display flashes.
Program control STOP
To stop Program control, press and hold the key for approx. 1 second during Program control.
Program control will stop, and the unit will revert to Standby (Program control waiting) mode.
Proceeding to the next step during Program control (Advance function)
By pressing the key for approx. 1 second during Program control, the performing step is
interrupted, proceeding to the next step. (Advance function)
While Wait function is working, the Wait function is cancelled, and proceeds to the next step.
If ‘ (Program control RUN/STOP)’ is selected in [Event input DI1 allocation], Program control
RUN/STOP can be switched by terminals 17-18 [DI1-COM]:
Signal edge action from OFF to ON / ON to OFF is engaged.
However, for the action when power is turned ON, Level action [ON (Closed) or OFF (Open)] is engaged.
17-18 [DI1-COM]:
OFF (Open)
Standby mode
Standby mode
17-18 [DI1-COM]:
ON (Closed)
Program control performs.
Program control Run
Program control Stop
(Standby mode)
17-18 [DI1-COM]:
OFF (Open)
Program control stops
(Standby mode).
Terminals 17-18
[DI1-COM]
OFF (Open)
Program control performs when
“17-18 [DI1-COM]” changes from
OFF (Open) to ON (Closed).
.
Program control stops (Standby mode)
when “17-18 [DI1-COM]” changes from
ON (Closed) to OFF (Open).
.
Terminals 17-18
[DI1-COM]
ON (Closed)
Controller status
(Fig. 8.7-7)