(Example) Selecting Program control and Setting program pattern of (Fig. 8.7-6)
Power ON
RUN mode
PV/SV Display
+ (3 sec)
Engineering mode
Set value lock
(Many times)
OUT/OFF key function
or
Select (Program control).
(Many times) or (3 sec)
RUN mode
Standby (Program control waiting)
Main setting mode
Step 1 SV
or
Set to 200 .
Step 1 time
or
Set to 1:00.
Step 1 wait value
or
Set to 10 .
Step 2 SV
or
Set to 200 .
Step 2 time
or
Set to 2:00.