User Manual
87
1
① ②
1:00 2:00
2
Program control Holding/Not holding
During Program control, progress of current step is suspended (on hold).
Fixed value control is performed using the SV from the point of suspension.
Program control Holding/Not holding can be selected in [Event input DI1/DI2 allocation].
Advance function
Interrupts current step while Program control is running, and proceeds to the beginning of the next
step.
By pressing the key for approx. 1 second during Program control, Advance function initiates.
Select this function in [Event input DI1/DI2 allocation].
Pattern end output
If Pattern end output is selected in [Event input DI1/DI2 allocation], pattern end output is turned ON
after Program control is finished, and the SV Display flashes .
By pressing the key for approx. 1 second, pattern end output is turned OFF, and the unit enters
Standby mode.
Step time unit
Step time unit can be selected: Hours:Minutes, Minutes:Seconds
Factory default value is Hours:Minutes.
Power Restore Action (Program control after power is restored)
If power fails during Program control, selects a status after the power is restored.
Factory default value is ‘Stops after power is restored’.
Power Restore Action
Description
Stops after power is
restored.
Stops Program control, and returns to Standby (Program control
waiting) mode.
Continues after power is
restored. (*)
Continues (resumes) Program control.
Suspends after power is
restored. (*)
Suspends (on hold) current program, and performs Fixed value
control using the SV from the point of suspension.
Pressing the key cancels suspension, and Program control
resumes.
(*) Progressing time error when power is restored: 10 minutes
This controller saves internal status every 10 minutes after Program control starts.
Internal status is also saved when step is changed.
When power is restored, the unit starts from the last auto-save point.
(Fig. 8.7-3)
Step number
Step time
Auto-save point (●)
Saves internal data every
10 minutes based on
program control start time.
PV start is used. SV and time are
advanced to the remaining time 0:52,
and program control starts.
If power failure occurs at
remaining time 0:28,
control resumes at ① 0:32.
で復帰します。
If power failure occurs at remaining time 1:45,
control resumes at ② 1:52.