User Manual
77
Characters,
Factory Default
Setting Item, Function, Setting Range
Indication time
• Sets time to backlight from no operation status until backlight is switched off.
Backlight relights by pressing any key while backlight is OFF.
• Setting range: 00:00 to 60:00 (Minutes:Seconds)
When set to 00:00, remains ON.
OUT1 MV preset value
• If ‘Preset output 1 ON/OFF’ or ‘Preset output 2 ON/OFF’ is selected in [Event
input allocation], OUT1 MV can be set.
Preset output 1 ON/OFF:
If sensor is burnt out during Event Input ON, control is performed with the preset
MV.
Preset output 2 ON/OFF:
When Event input is ON, control is performed with the preset MV.
• Setting range: 0.0 to 100.0% (Direct current output: -5.0 to 105.0%)
For BCS2, available only when Event input (EIW, EIT, EI options) is ordered.
For BCR2/BCD2, available when Serial communication (C5W option) or Event input (EIW, EIT, EI options) is
ordered.
OUT2 MV preset value
• If ‘Preset output 1 ON/OFF’ or ‘Preset output 2 ON/OFF’ is selected in [Event
input allocation], OUT2 MV can be set.
Preset output 1 ON/OFF:
If sensor is burnt out during Event Input ON, control is performed with the preset
MV.
Preset output 2 ON/OFF:
When Event input is ON, control is performed with the preset MV.
• Setting range: 0.0 to 100.0% (Direct current output: -5.0 to 105.0%)
Available for the following cases:
• For BCS2, Event output EV2 (EV2 option), Heating/Cooling control (DS, DA) or Event input (EIW, EIT, EI
options) is ordered.
• For BCR2/BCD2, Event output EV2 (EV2 option), Heating/Cooling control (DS, DA), Serial communication
(C5W option) or Event input (EIW, EIT, EI options) is ordered.
• When (Heating/Cooling control relay contact output) is selected in [Event output EV2 allocation].
Controller/Converter function
• Selects either controller or converter function.
• Selection item:
Controller
Converter
Available only when OUT1 is Direct current output.