Setting Item, Function, Setting Range
External setting input high limit
• Sets External setting input high limit value.
(This value corresponds to 20 mA in Direct current input.)
• Setting range: External setting input low limit to Input range high limit
Available only when External setting input (EIT option) is ordered.
External setting input low limit
• Sets External setting input low limit value.
(This value corresponds to 4 mA in Direct current input.)
• Setting range: Input range low limit to External setting input high limit
Available only when External setting input (EIT option) is ordered.
Remote bias
• During remote action, SV includes the remote bias value.
• Setting range: Converted value of 20% of the input span
DC voltage, current inputs: 20% of the scaling span (*1)
Available only when External setting input (EIT option) is ordered.
Transmission output type
• Selects the transmission output type.
When changing transmission output type, refer to Section 8.10 Items to be
Initialized by Changing Settings (p.96).
Selection item:
PV transmission
SV transmission
MV transmission
DV transmission
Available only when Transmission output (EIT option) is ordered.
Transmission output high limit
Sets the Transmission output high limit value.
(This value correponds to 20 mA in Direct current output.)
Setting range:
PV, SV transmission
Transmission output low limit to Input range high limit value
MV transmission
Transmission output low limit to 105.0%
DV transmission
Transmission output low limit to Scaling span (*1)
Available only when Transmission output (EIT option) is ordered.
Transmission output low limit
Sets the Transmission output low limit value.
(This value correponds to 4 mA in Direct current output.)
Setting range:
PV, SV transmission
Input range low limit to Transmission output high limit value
MV transmission
-5.0% to Transmission output high limit value
DV transmission
-Scaling span to Transmission output high limit value (*1)
Available only when Transmission output (EIT option) is ordered.
Step time unit
• Selects the Step time unit for the Program control.
Selection item:
Hours:Minutes
Minutes:Seconds
Available only when Program control is selected in [OUT/OFF key function].
(*1) The placement of the decimal point follows the selection.