User Manual
65
Characters,
Factory Default
Setting Item, Function, Setting Range
Event input DI1 allocation
• Selects Event input DI1 from the Event Input Allocation Table.
Corresponds to [Event input DI1 allocation] in Initial setting mode.
• Selection item:
Event Input Allocation Table
Event input
function
Input ON
(Closed)
Input OFF
(Open)
Remarks
No event
Set value memory
Control ON/OFF
Control OFF
Control ON
Control output OFF
function
Direct/Reverse
action
Direct action
Reverse
action
Always effective
Preset output 1
ON/OFF
Preset output
Usual control
If sensor is burnt
out, the unit
maintains control
with the preset MV.
Preset output 2
ON/OFF
Preset output
Usual control
The unit maintains
control with the
preset MV.
Auto/Manual
control
Manual
control
Automatic
control
Remote/Local
Remote
Local
Effective only when
EIT (External setting
input) option is
ordered.
Program control
RUN/STOP
RUN
STOP
Level action when
power-on
Program control
Holding/Not
holding
Holding
Not holding
Level action when
power-on
Program control
Advance function
Advance
function
Usual control
Level action when
power-on
Integral action
holding
Integral action
holding
Usual
integral action
Control continues
with the integral
value being held.
For BCS2, available only when Event input (EIW, EIT, EI options) is ordered.
For BCR2/BCD2, available when Serial communication (C5W option) or Event input (EIW, EIT, EI options) is
ordered.
Event input DI2 allocation
• Selects Event input DI2 from the Event Input Allocation Table.
Corresponds to [Event input DI2 allocation] in Initial setting mode.
• Selection item: Same as Event input DI1 allocation
For BCS2, available only when Event input (EIW, EI options) is ordered.
For BCR2/BCD2, available when Serial communication (C5W option) or Event input (EIW, EIT, EI options) is
ordered.