User Manual
62
Characters,
Factory Default
Setting Item, Function, Setting Range
EV1 high limit alarm value
• Sets EV1 high limit alarm value.
This value is available only for the following cases:
(Alarm output, High/Low limits independent alarm), (Alarm
output, High/Low limit range independent alarm), or (Alarm output,
High/Low limits with standby independent alarm) is selected in [Event output EV1
allocation].
Corresponds to [EV1 high limit alarm value] in Initial setting mode.
• Setting range: Same as those of EV1 alarm value
EV2 alarm value
• Sets EV2 alarm value.
Corresponds to [EV2 alarm value] in Initial setting mode.
EV2 alarm value matches EV2 low limit alarm value in the following cases:
(Alarm output, High/Low limits independent alarm), (Alarm
output, High/Low limit range independent alarm), or (Alarm output
High/Low limits with standby independent alarm) is selected in [Event output EV2
allocation].
• Setting range: Same as those of EV1 alarm value
Available only when (Alarm output, High limit alarm) to (Alarm output, High/Low limits with
standby independent alarm) is selected in [Event output EV2 allocation].
EV2 high limit alarm value
• Sets EV2 high limit alarm value.
This value is available only for the following cases:
(Alarm output, High/Low limits independent alarm), (Alarm
output, High/Low limit range independent alarm), or (Alarm output,
High/Low limits with standby independent alarm) is selected in [Event output EV2
allocation].
Corresponds to [EVT2 high limit alarm value] in Initial setting mode.
• Setting range: Same as those of EV1 alarm value
and CT1
current value are
alternately
indicated in the
PV Display.
Heater burnout alarm 1 value
• Sets the heater current value for Heater burnout alarm 1.
Corresponds to [Heater burnout alarm 1 value] in Initial setting mode.
Characters and CT1 current value are indicated alternately in the PV Display.
When OUT1 is ON, the CT1 current value is updated.
When OUT1 is OFF, the unit memorizes the previous value when OUT1 was ON.
Upon returning to set limits, the alarm will stop.
• Setting range:
20.0 A: 0.0 to 20.0 A
100.0 A: 0.0 to 100.0 A
Setting to 0.0 disables the alarm.
Available only when Heater burnout alarm (C5W, EIW, W options) is ordered.