OUT2 proportional band
Air cooling
Oil cooling
Water cooling
Characters,
Factory Default
Setting Item, Function, Setting Range
OUT2 cooling method
• Selects OUT2 cooling method from air, oil or water cooling.
(Fig. 7.2-1)
• Selection item:
Air cooling (linear characteristics)
Oil cooling (1.5th power of the linear characteristics)
Water cooling (2nd power of the linear characteristics)
Available when Event output EV2 (EV2 option) or Heating/Cooling control (DS, DA options) is ordered.
Not available if OUT2 is in ON/OFF control.
OUT2 proportional band
• Sets the proportional band for OUT2.
Setting range: 0 to Input span ( )
DC voltage, current inputs: 0.0 to 1000.0%
OUT2 becomes ON/OFF control when set to 0 or 0.0.
Available when Event output EV2 (EV2 option) or Heating/Cooling control (DS, DA options) is ordered.
Not available if OUT1 is in ON/OFF control.
OUT2 proportional cycle
• Sets proportional cycle for OUT2.
For relay contact output, if the proportional cycle time is decreased, the frequency
of the relay action increases, and the life of the relay contact is shortened.
• Setting range: 0.5, or 1 to 120 seconds
Available when Event output EV2 (EV2 option) or Heating/Cooling control (DS, DA options) is ordered.
Not available for Direct current output type, or if OUT2 is in ON/OFF control.
OUT2 ON/OFF hysteresis
• Sets ON/OFF hysteresis for OUT2.
• Setting range: 0.1 to 1000.0 ( ),
DC voltage, current inputs: 1 to 10000 (*1)
Available when Event output EV2 (EV2 option) or Heating/Cooling control (DS, DA options) is ordered.
OUT2 high limit
• Sets OUT2 high limit value.
• Setting range: OUT2 low limit value to 100%
(Direct current output type: OUT2 low limit value to 105%)
Available when Event output EV2 (EV2 option) or Heating/Cooling control (DS, DA options) is ordered.
(*1) The placement of the decimal point follows the selection.