User Manual

54
Characters,
Factory Default
Setting Item, Function, Setting Range
SV2
• Sets SV2.
Corresponds to [SV2] in Initial setting mode.
If Program control is selected in [OUT/OFF key function], this will become Step 2
SV.
• Setting range: Scaling low limit to Scaling high limit (*1)
Available for the following cases:
When Program control is selected in [OUT/OFF key function]
For BCS2, Event input (EIW, EIT, EI options) is ordered
For BCR2/BCD2, Serial communication (C5W option) or Event input (EIW, EIT, EI options) is ordered.
When (Set value memory) is selected in [Event input DI1/DI2 allocation].
Step 2 time
• Sets Step 2 time.
• Setting range: , or 00:00 to 99:59
If is set, Step 2 time will be held, and Fixed value control will be performed
using Step 2 SV.
Available only when Program control is selected in [OUT/OFF key function].
Step 2 wait value
• Sets Step 2 wait value.
• Setting range: 0 to Converted value of 20% of the input span
DC voltage, current inputs: 0 to Converted value of 20% of scaling span (*1)
Setting the value to 0 disables Wait function.
Available only when Program control is selected in [OUT/OFF key function].
SV3
• Sets SV3.
Corresponds to [SV3] in Initial setting mode.
If Program control is selected in [OUT/OFF key function], this will become Step 3
SV.
• Setting range: Scaling low limit to Scaling high limit (*1)
Available for the following cases:
When Program control is selected in [OUT/OFF key function]
For BCS2, Event input (EIW, EI options) is ordered
For BCR2/BCD2, Serial communication (C5W option) or Event input (EIW, EIT, EI options) is ordered.
When (Set value memory) is selected in [Event input DI1/DI2 allocation].
Step 3 time
• Sets Step 3 time.
• Setting range: , or 00:00 to 99:59
If is set, Step 3 time will be held, and Fixed value control will be performed
using Step 3 SV.
Available only when Program control is selected in [OUT/OFF key function].
Step 3 wait value
• Sets Step 3 wait value.
• Setting range: 0 to Converted value of 20% of the input span
DC voltage, current inputs: 0 to Converted value of 20% of scaling span (*1)
Setting the value to 0 disables Wait function.
Available only when Program control is selected in [OUT/OFF key function].
(*1) The placement of the decimal point follows the selection.