User Manual
51 
[Event Input] 
• If    (Set value memory) is selected, the set value memory number will be as follows. 
When only Event input DI1 is selected. 
Set value memory number 
SV1 
SV2 
DI1 
Open 
Closed 
When only Event input DI2 is selected. 
Set value memory number 
SV1 
SV2 
DI2 
Open 
Closed 
When both Event inputs DI1, DI2 are selected. 
Set value memory number 
SV1 
SV2 
SV3 
SV4 
DI1 
Open 
Closed 
Open 
Closed 
DI2 
Open 
Open 
Closed 
Closed 
• Preset value of    (Preset output 1 ON/OFF) and    (Preset output 2 ON/OFF) 
can be set in [OUT1, OUT2 MV preset value] in Engineering mode (p.77).   
• If    (Preset output 2 ON/OFF) is selected in [Event input DI1 allocation], and     
(Auto/Manual control) is selected in Event input DI2 allocation, and if DI1-COM and DI2-COM terminals 
are turned ON (Closed) simultaneously, then Preset output 2 will be given priority, and control starts 
with the MV set in [OUT1/OUT2 MV preset value (p.77)] in Engineering mode. 
In this case, control will be switched to manual control, and MV cannot be changed via keypad 
• Signal edge action from OFF to ON / ON to OFF is engaged. 
If    (Program control RUN/STOP) is selected in [Event input DI1 allocation], the following 
action will be performed. 
However, only when power is turned ON, Level action [ON (Closed) or OFF (Open)] is engaged. 
  (Fig. 6.2-3) 
• OR calculation [if any one is ON (closed), the function activates] begins if the same functions except 
  (Set value memory) have been selected in [Event input DI1/DI2 allocation]. 
If any terminals DI1-COM or DI2-COM is ON (closed), the function activates. 
17-18 [DI1-COM]:   
OFF (Open) 
Standby mode 
Standby mode 
17-18 [DI1-COM]: 
ON (Closed) 
Program control performs. 
Program control Run 
Program control Stop 
(Standby mode) 
17-18 [DI1-COM]:   
OFF (Open) 
Program control stops 
(Standby mode). 
Terminals 17-18   
[DI1-COM] OFF (Open) 
Program control performs when 
“17-18 [DI1-COM]” changes from 
OFF (Open) to ON (Closed). 
  . 
Program  control  stops  (Standby  mode) 
when  “17-18  [DI1-COM]” changes  from 
ON (Closed) to OFF (Open). 
  . 
Terminals 17-18   
[DI1-COM] ON (Closed) 
Controller status 