[Event Input]
If (Set value memory) is selected, the set value memory number will be as follows.
When only Event input DI1 is selected.
Set value memory number
SV1
SV2
DI1
Open
Closed
When only Event input DI2 is selected.
Set value memory number
SV1
SV2
DI2
Open
Closed
When both Event inputs DI1, DI2 are selected.
Set value memory number
SV1
SV2
SV3
SV4
DI1
Open
Closed
Open
Closed
DI2
Open
Open
Closed
Closed
Preset value of (Preset output 1 ON/OFF) and (Preset output 2 ON/OFF)
can be set in [OUT1, OUT2 MV preset value] in Engineering mode (p.77).
If (Preset output 2 ON/OFF) is selected in [Event input DI1 allocation], and
(Auto/Manual control) is selected in Event input DI2 allocation, and if DI1-COM and DI2-COM terminals
are turned ON (Closed) simultaneously, then Preset output 2 will be given priority, and control starts
with the MV set in [OUT1/OUT2 MV preset value (p.77)] in Engineering mode.
In this case, control will be switched to manual control, and MV cannot be changed via keypad
Signal edge action from OFF to ON / ON to OFF is engaged.
If (Program control RUN/STOP) is selected in [Event input DI1 allocation], the following
action will be performed.
However, only when power is turned ON, Level action [ON (Closed) or OFF (Open)] is engaged.
(Fig. 6.2-3)
OR calculation [if any one is ON (closed), the function activates] begins if the same functions except
(Set value memory) have been selected in [Event input DI1/DI2 allocation].
If any terminals DI1-COM or DI2-COM is ON (closed), the function activates.
17-18 [DI1-COM]:
OFF (Open)
Standby mode
Standby mode
17-18 [DI1-COM]:
ON (Closed)
Program control performs.
Program control Run
Program control Stop
(Standby mode)
17-18 [DI1-COM]:
OFF (Open)
Program control stops
(Standby mode).
Terminals 17-18
[DI1-COM] OFF (Open)
Program control performs when
17-18 [DI1-COM] changes from
OFF (Open) to ON (Closed).
.
Program control stops (Standby mode)
when 17-18 [DI1-COM] changes from
ON (Closed) to OFF (Open).
.
Terminals 17-18
[DI1-COM] ON (Closed)
Controller status