Characters,
Factory Default
Setting Item, Function, Setting Range
Transmission output high limit
Sets the Transmission output high limit value.
This value correponds to 20 mA in DC current output.
Setting range:
PV, SV transmission
Transmission output low limit to Input range high limit value
DC voltage, current inputs: -2000 to 10000
MV transmission
Transmission output low limit value to 105.0%
DV transmission
Transmission output low limit to Scaling span (*1)
Available only when Transmission output (EIT option) is ordered.
Transmission output low limit
Sets the Transmission output low limit value.
This value correponds to 4 mA in DC current output.
Selection item:
PV, SV transmission
Input range low limit to Transmission output high limit value
DC voltage, current inputs: -2000 to 10000
MV transmission
-5.0% to Transmission output high limit value
DV transmission
-Scaling span to Transmission output high limit value (*1)
Available only when Transmission output (EIT option) is ordered.
SV1
• Sets SV1.
• Setting range: Scaling low limit to Scaling high limit (*1)
Available when Control output OFF function or Auto/Manual control is selected in [OUT/OFF key function].
SV2
• Sets SV2.
• Setting range: Scaling low limit to Scaling high limit (*1)
Available for the following cases:
When Control output OFF function or Auto/Manual control is selected in [OUT/OFF key function].
For BCS2, Event input (EIW, EIT, EI options) is ordered.
For BCR2/BCD2, Serial communication (C5W option) or Event input (EIW, EIT, EI options) is ordered.
When (Set value memory) is selected in [Event input DI1/DI2 allocation].
SV3
• Sets SV3.
• Setting range: Scaling low limit to Scaling high limit (*1)
Available for the following cases:
When Control output OFF function or Auto/Manual control is selected in [OUT/OFF key function].
For BCS2, Event input (EIW, EI options) is ordered.
For BCR2/BCD2, Serial communication (C5W option) or Event input (EIW, EIT, EI options) is ordered.
When (Set value memory) is selected in [Event input DI1/DI2 allocation].
SV4
• Sets SV4.
• Setting range: Scaling low limit to Scaling high limit (*1)
Available for the following cases:
When Control output OFF function or Auto/Manual control is selected in [OUT/OFF key function].
For BCS2, Event input (EIW, EI options) is ordered
For BCR2/BCD2, Serial communication (C5W option) or Event input (EIW, EIT, EI options) is ordered.
When (Set value memory) is selected in [Event input DI1/DI2 allocation].
(*1) The placement of the decimal point follows the selection.