User Manual

48
Characters,
Factory Default
Setting Item, Function, Setting Range
Event input
function
Input ON
(Closed)
Input OFF
(Open)
Remarks
Remote/Local
Remote
Local
Effective only when
EIT (External setting
input) option is
ordered
Program control
RUN/STOP
RUN
STOP
Level action when
power-on
Program control
Holding/Not
holding
Holding
Not holding
Level action when
power-on
Program control
Advance function
Advance
function
Usual
control
Level action when
power-on
Integral action
Holding
Integral
action
Holding
Usual
integral
action
Control continues
with the integral
value being held.
For BCS2, available only when Event input (EIW, EITEI options) is ordered.
For BCR2/BCD2, available when Serial communication (C5W option) or Event input (EIW, EIT, EI options) is
ordered.
Event input DI2 allocation
Selects Event input DI2 from Event Input Allocation Table.
(Refer to Event Input on p.51)
Selection item:
Same as those of Event input DI1 allocation
For BCS2, available only when Event input (EIW, EI option) is ordered.
For BCR2/BCD2, available when Serial communication (C5W option) or Event input (EIW, EIT, EI options) is
ordered.
External setting input high limit
• Sets External setting input high limit value.
This value corresponds to 20 mA in Direct current input.
• Setting range: External setting input low limit to Input range high limit (*1)
Available only when External setting input (EIT option) is ordered.
External setting input low limit
• Sets External setting input low limit value.
This value corresponds to 4 mA in Direct current input.
• Setting range: Input range low limit to External setting input high limit (*1)
Available only when External setting input (EIT option) is ordered.
Transmission output type
• Selects transmission output type.
When changing transmission output type, refer to Section 8.10 Items to be
Initialized by Changing Settings (p.96).
Selection item:
PV transmission
SV transmission
MV transmission
DV transmission
Available only when Transmission output (EIT option) is ordered.
(*1) The placement of the decimal point follows the selection.