User Manual
48 
Characters, 
Factory Default 
Setting Item, Function, Setting Range 
Event input 
function 
Input ON 
(Closed) 
Input OFF 
(Open) 
Remarks 
Remote/Local 
Remote 
Local 
Effective only when 
EIT (External setting 
input) option is   
ordered 
Program control 
RUN/STOP 
RUN 
STOP 
Level action when 
power-on 
Program control 
Holding/Not 
holding 
Holding 
Not holding 
Level action when 
power-on 
Program control 
Advance function 
Advance 
function 
Usual 
control 
Level action when 
power-on 
Integral action   
Holding 
Integral 
action 
Holding 
Usual 
integral 
action 
Control continues 
with the integral 
value being held. 
For BCS2, available only when Event input (EIW, EIT、EI options) is ordered. 
For BCR2/BCD2, available when Serial communication (C5W option) or Event input (EIW, EIT, EI options) is 
ordered. 
Event input DI2 allocation 
• Selects Event input DI2 from Event Input Allocation Table.   
(Refer to ‘Event Input’ on p.51) 
• Selection item:   
Same as those of Event input DI1 allocation 
For BCS2, available only when Event input (EIW, EI option) is ordered. 
For BCR2/BCD2, available when Serial communication (C5W option) or Event input (EIW, EIT, EI options) is 
ordered. 
External setting input high limit 
• Sets External setting input high limit value.   
This value corresponds to 20 mA in Direct current input. 
• Setting range: External setting input low limit to Input range high limit (*1) 
Available only when External setting input (EIT option) is ordered. 
External setting input low limit 
• Sets External setting input low limit value. 
This value corresponds to 4 mA in Direct current input. 
• Setting range: Input range low limit to External setting input high limit (*1) 
Available only when External setting input (EIT option) is ordered. 
Transmission output type 
• Selects transmission output type. 
• When changing transmission output type, refer to Section “8.10 Items to be 
  Initialized by Changing Settings” (p.96). 
• Selection item: 
PV transmission 
SV transmission 
MV transmission 
DV transmission 
Available only when Transmission output (EIT option) is ordered. 
(*1) The placement of the decimal point follows the selection. 