User Manual
47 
Characters, 
Factory Default 
Setting Item, Function, Setting Range 
  and CT2 
current value are 
alternately 
indicated in the 
PV Display. 
Heater burnout alarm 2 value 
• Sets the heater current value for Heater burnout alarm 2. 
Available only when using 3-phase. 
Characters    and CT2 current value are alternately indicated in the PV Display. 
When OUT1 is ON, the CT2 current value is updated.   
When OUT1 is OFF, the unit memorizes the previous value when OUT1 was ON. 
Upon returning to set limits, the alarm will stop. 
• Setting range: 
20 A: 0.0 to 20.0 A   
100 A: 0.0 to 100.0 A 
Setting to 0.0 disables the alarm. 
Not available for the Direct current output type. 
Available only when Heater burnout alarm (C5W, EIW, W options) is ordered. 
Loop break alarm time 
• Sets the time to assess the Loop break alarm. 
Refer to ‘Loop Break Alarm’ on p.50. 
• Setting range: 0 to 200 minutes 
Setting to 0 (zero) disables the alarm. 
Loop break alarm span 
• Sets the temperature to assess the Loop break alarm. 
Refer to ’Loop Break Alarm’ on p.50. 
• Setting range: 0 to 150   ( ), or 0.0 to 150.0   ( )   
DC voltage, current inputs: 0 to 1500 (*1)   
Setting to 0 (zero) disables the alarm. 
Event input DI1 allocation 
• Selects Event input DI1 from Event Input Allocation Table. 
  (Refer to ’Event Input’ on p.51.) 
• Selection item: 
Event Input Allocation Table 
Event input 
function 
Input ON 
(Closed) 
Input OFF 
(Open) 
Remarks 
No event 
Set value memory 
Control ON/OFF 
Control OFF 
Control ON 
Control output OFF 
function 
Direct/Reverse   
action 
Direct action 
Reverse 
action 
Always effective 
Preset output 1   
ON/OFF 
Preset 
output 
Usual 
control 
If sensor is burnt out, 
the unit maintains 
control with the 
preset MV. 
Preset output 2   
ON/OFF 
Preset 
output 
Usual 
control 
The unit maintains 
control with the   
preset MV. 
Auto/Manual 
control 
Manual 
control 
Automatic 
control 
(*1) The placement of the decimal point follows the selection. 