EV1 alarm hysteresis 
• Sets EV1 alarm hysteresis. 
• Setting range: 0.1 to 1000.0   ( ),   
DC voltage, current inputs: 1 to 10000 (*1) 
Available when any alarm from    (Alarm output, High limit alarm) to    (Alarm output, High/Low 
limits with standby independent alarm) is selected in [Event output EV1 allocation]. 
EV1 alarm delay time 
• Sets EV1 alarm action delay time. 
When setting time has elapsed after the input enters the alarm output range, the 
alarm is activated. 
• Setting range: 0 to 10000 seconds 
Available when any alarm from    (Alarm output, High limit alarm) to    (Alarm output, High/Low 
limits with standby independent alarm) is selected in [Event output EV1 allocation]. 
EV1 alarm Energized/De-energized 
• Selects Energized/De-energized status for EV1 alarm. 
(Refer to ‘EV1/EV2 Energized/De-energized’ on p.50.) 
• Selection item: 
Energized 
De-energized 
Available when any alarm from    (Alarm output, High limit alarm) to    (Alarm output, High/Low 
limits with standby independent alarm) is selected in [Event output EV1 allocation]. 
TS1 output step number 
• Sets the step number at which Time signal output TS1 will be turned OFF or ON 
  during Program control.   
(Refer to ‘Time Signal Output’ on p.52.) 
• Setting range: 1 to 9   
Available only when    (Time signal output) is selected in [Event output EV1 allocation]. 
TS1 OFF time 
• Sets Time signal output TS1 OFF time. 
  (Refer to ‘Time Signal Output’ on p.52.) 
• Setting range: 00:00 to 99:59 (*4)   
Available only when    (Time signal output) is selected in [Event output EV1 allocation]. 
TS1 ON time 
• Sets Time signal output TS1 ON time. 
  (Refer to ‘Time Signal Output’ on p.52.) 
• Setting range: 00:00 to 99:59 (*4) 
Available only when    (Time signal output) is selected in [Event output EV1 allocation]. 
(*1)The placement of the decimal point follows the selection. 
(*4) Time unit follows the selection from [Step time unit]. 