User Manual

42
Characters,
Factory Default
Setting Item, Function, Setting Range
EV1 alarm value 0 Enabled/Disabled
When EV1 alarm value is 0 (zero), alarm action can be Enabled or Disabled.
Selection item:
Disabled
Enabled
Available when (Alarm output, High limit alarm) to (Alarm output, High/Low limit range
independent alarm), (Alarm output, High limit with standby alarm) to (Alarm output,
High/Low limits with standby independent alarm) are selected in [Event output EV1 allocation].
EV1 alarm value
• Sets EV1 alarm value.
EV1 alarm value matches EV1 low limit alarm value in the following cases:
(Alarm output, High/Low limits independent alarm), (Alarm
output, High/Low limit range independent alarm), or (Alarm output,
High/Low limits with standby independent alarm) is selected in [Event output EV1
allocation].
Setting range:
High limit alarm
-(Input span) to Input span ( ) (*1) (*2)
Low limit alarm
-(Input span) to Input span ( ) (*1) (*2)
High/Low limits alarm
0 to Input span ( ) (*1) (*2)
High/Low limits independent
alarm
0 to Input span ( ) (*1) (*2)
High/Low limit range alarm
0 to Input span ( ) (*1) (*2)
High/Low limit range
independent alarm
0 to Input span ( ) (*1) (*2)
Process high alarm
Input range low limit to Input range high limit (*1) (*3)
Process low alarm
Input range low limit to Input range high limit (*1) (*3)
High limit with standby alarm
-(Input span) to Input span ( ) (*1) (*2)
Low limit with standby alarm
-(Input span) to Input span ( ) (*1) (*2)
High/Low limits with standby
alarm
0 to Input span ( ) (*1) (*2)
High/Low limits with standby
independent alarm
0 to Input span ( ) (*1) (*2)
Available when any alarm from (Alarm output, High limit alarm) to (Alarm output, High/Low
limits with standby independent alarm) is selected in [Event output EV1 allocation].
EV1 high limit alarm value
Sets EV1 high limit alarm value.
This value is available only for the following cases.
(Alarm output, High/Low limits independent alarm), (Alarm
output, High/Low limit range independent alarm), or (Alarm output,
High/Low limits with standby independent alarm) is selected in [Event output EV1
allocation].
Setting range: Same as those of EV1 alarm value
(*1) The placement of the decimal point follows the selection.
(*2) For DC voltage, current inputs, the input span is the same as the scaling span.
(*3) For DC voltage, current inputs, input range low (or high) limit value is the same as scaling low (or high) limit value.