6.2 Initial Setting Mode 
To enter Initial setting mode, press and hold the    and    keys (in that order) for 3 seconds in RUN mode.   
To set (or select) each setting item, use the    or    key. 
To register each setting item, press the    key. 
Explanation of setting item: 
• Upper left: PV Display: Indicates setting characters. 
• Lower left: SV Display: Indicates factory default. 
• Right side: Indicates the setting item, explanation of its function, and setting range (or selection item). 
Input type 
• Selects an input type from thermocouple (10 types), RTD (2 types), Direct current 
  (2 types) and DC voltage (4 types), and the unit  / . 
Characters, 
Factory Default 
Setting Item, Function, Setting Range 
Input type 
• Selects an input type from thermocouple (10 types), RTD (2 types), Direct current 
  (2 types) and DC voltage (4 type), and the unit  / . 
• When changing the input from DC voltage to other inputs, remove the sensor 
  connected to this controller first, then change the input. If the input is changed 
  with the sensor connected, the input circuit may break. 
• When changing an input type, refer to Section “8.10 Items to be Initialized by 
Changing Settings” (p.96). 
• Selection item: 
K    -200 to 1370  
K    -328 to 2498  
K    -200.0 to 400.0  
K    -328.0 to 752.0  
J    -200 to 1000  
J    -328 to 1832  
R        0 to 1760  
R      32 to 3200  
S        0 to 1760  
S      32 to 3200  
B        0 to 1820  
B      32 to 3308  
E    -200 to 800  
E    -328 to 1472  
T    -200.0 to 400.0  
T    -328.0 to 752.0  
N    -200 to 1300  
N    -328 to 2372  
PL-     0 to 1390  
PL-   32 to 2534  
C(W/Re5-26)    0 to 2315  
C(W/Re5-26)    32 to 4199  
Pt100    -200.0 to 850.0  
Pt100       -328.0 to1562.0  
JPt100    -200.0 to 500.0  
JPt100     -328.0 to 932.0  
Pt100    -200 to 850  
Pt100      -328 to 1562  
JPt100    -200 to 500  
JPt100    -328 to 932  
4 to 20 mA DC -2000 to 10000 
0 to 20 mA DC -2000 to 10000 
0 to 1 V DC    -2000 to 10000 
0 to 5 V DC    -2000 to 10000 
1 to 5 V DC    -2000 to 10000 
0 to 10 V DC    -2000 to 10000 
Scaling high limit 
• Sets scaling high limit value. 
• Setting range: Scaling low limit value to Input range high limit value 
DC voltage, current inputs: -2000 to 10000 (*1) 
(*1) The placement of the decimal point follows the selection. 
Setting characters 
Factory default value 
Setting item name, function, setting range (or selection item) 