User Manual

36
[Output status when input errors occur] can be used only for controllers using Direct current and
voltage inputs, and Direct current output.
Output status differs depending on selection in [Output status when input errors occur].
Output status
when input
errors occur
Contents,
Indication
Output Status
OUT1
OUT2
Direct (Cooling)
action
Reverse (Heating)
action
Direct (Cooling)
action
Reverse (Heating)
action
Indicates
[ ]
and
[ ]
alternately.
ON (20mA) or
OUT1 high
limit value (*)
OFF (4mA) or
OUT1 low limit
value
OFF or
OUT2 low
limit value
ON or
OUT2 high
limit value (*)
OFF (4mA) or
OUT1 low
limit value
OFF or
OUT2 low
limit value
Indicates
[ ]
and
[ ]
alternately.
OFF (4mA) or
OUT1 low
limit value
ON (20mA) or
OUT1 high limit
value (*)
ON or
OUT2 high
limit value (*)
OFF or
OUT2 low
limit value
OFF (4mA) or
OUT1 low limit
value
OFF or
OUT2 low
limit value
(*) Outputs a value between OFF (4mA) and ON (20mA) or between OUT1 (or OUT2) low limit value and OUT1 (or OUT2)
high limit value, depending on deviation.