User Manual

17
BCR2, BCD2
Mount the controller vertically to the flat, rigid panel to ensure it adheres to the Drip-proof/Dust-proof
specification (IP66).
Mountable panel thickness: 1 to 7 mm
(1) For the BCR2, if Drip-proof/Dust-proof specification (IP66) is necessary, mount the included
gasket.
If lateral close mounting is used for the controller, IP66 specification (Drip-proof/Dust-proof)
may be compromised, and all warranties will be invalidated.
If Drip-proof/Dust-proof specification (IP66) is not necessary, it is not necessary to mount the
gasket.
(2) Insert the controller from the front side of the control panel. (Fig. 3.4.1-3)
(Fig. 3.4.1-3)
(3) Attach the mounting brackets by the holes at the top and bottom of the case,
and secure the controller in place with the screws.
The torque is approximately 0.1 Nm.
(Fig. 3.4.1-4)
Screw type
mounting bracket
Gasket