User Manual
145 
Characters, 
Factory Default 
Setting Item, Setting Range 
EV2 alarm value 
High limit alarm 
-(Input span) to Input span    ( ) (*1) (*2) 
Low limit alarm 
-(Input span) to Input span    ( ) (*1) (*2) 
High/Low limits alarm 
0 to Input span    ( ) (*1) (*2) 
High/Low limits independent 
alarm 
0 to Input span    ( ) (*1) (*2) 
High/Low limit range alarm 
0 to Input span    ( ) (*1) (*2) 
High/Low limit range   
independent alarm 
0 to Input span    ( ) (*1) (*2) 
Process high alarm 
Input range low limit to Input range high limit (*1) (*3) 
Process low alarm 
Input range low limit to Input range high limit (*1) (*3) 
High limit with standby alarm 
-(Input span) to Input span    ( ) (*1) (*2) 
Low limit with standby alarm 
-(Input span) to Input span    ( ) (*1) (*2) 
High/Low limits with standby 
alarm 
0 to Input span    ( ) (*1) (*2) 
High/Low limits with standby 
independent alarm 
0 to Input span    ( ) (*1) (*2) 
EV2 high limit alarm value 
 Setting range: Same as those of EV2 alarm value 
EV2 alarm hysteresis 
 Setting range: 0.1 to 1000.0   ( ),   
DC voltage, current inputs: 1 to 10000 (*1) 
EV2 alarm delay time 
 Setting range: 0 to 10000 seconds 
EV2 alarm Energized/De-energized 
Energized 
De-energized 
TS2 output step number 
 Setting range: 1 to 9 
TS2 OFF time 
 Setting range: 00:00 to 99:59 (*4) 
TS2 ON time 
 Setting range: 00:00 to 99:59 (*4) 
Sensor correction coefficient 
 Setting range: -10.000 to 10.000 
Sensor correction 
 Setting range: -1000.0 to 1000.0   ( )   
DC voltage, current inputs: -10000 to 10000 (*1) 
PV filter time constant 
 Setting range: 0.0 to 10.0 seconds 
(*1) The placement of the decimal point follows the selection. 
(*2) For DC voltage, current inputs, the input span is the same as the scaling span. 
(*3) For DC voltage, current inputs, input range low (or high) limit value is the same as scaling low (or high) limit value. 
(*4) Time unit follows the selection from [Step time unit]. 