User Manual

141
Characters,
Factory Default
Setting Item, Setting Range
Overlap/Dead band
Setting range: -200.0 to 200.0 ( ),
DC voltage, current inputs: -2000 to 2000 (*1)
Direct/Reverse action
Reverse (Heating) action
Direct (Cooling) action
EV1 alarm value
High limit alarm
-(Input span) to Input span ( ) (*1) (*2)
Low limit alarm
-(Input span) to Input span ( ) (*1) (*2)
High/Low limits alarm
0 to Input span ( ) (*1) (*2)
High/Low limits independent
alarm
0 to Input span ( ) (*1) (*2)
High/Low limit range alarm
0 to Input span ( ) (*1) (*2)
High/Low limit range
independent alarm
0 to Input span ( ) (*1) (*2)
Process high alarm
Input range low limit to Input range high limit (*1) (*3)
Process low alarm
Input range low limit to Input range high limit (*1) (*3)
High limit with standby alarm
-(Input span) to Input span ( ) (*1) (*2)
Low limit with standby alarm
-(Input span) to Input span ( ) (*1) (*2)
High/Low limits with standby
alarm
0 to Input span ( ) (*1) (*2)
High/Low limits with standby
independent alarm
0 to Input span ( ) (*1) (*2)
EV1 high limit alarm value
Setting range: Same as those of EV1 alarm value
EV2 alarm value
Setting range: Same as those of EV1 alarm value
EV2 high limit alarm value
Setting range: Same as those of EV1 alarm value
and CT1 current
value are alternately
indicated in the PV
Display.
Heater burnout alarm 1 value
Setting range:
20.0 A: 0.0 to 20.0 A
100.0 A: 0.0 to 100.0 A
and CT2 current
value are alternately
indicated in the PV
Display.
Heater burnout alarm 2 value
Setting range:
20.0 A: 0.0 to 20.0 A
100.0 A: 0.0 to 100.0 A
Loop break alarm time
Setting range: 0 to 200 minutes
Loop break alarm span
Setting range: 0 to 150 ( ), 0.0 to 150.0 ( )
DC voltage, current inputs: 0 to 1500 (*1)
(*1) The placement of the decimal point follows the selection.
(*2) For DC voltage, current inputs, the input span is the same as the scaling span.
(*3) For DC voltage, current inputs, input range low (or high) limit value is the same as scaling low (or high) limit value.