13.6 Sub Setting Mode 
The PV Display indicates setting characters, and the SV Display indicates factory default value. 
Characters, 
Factory Default 
Setting Item, Setting Range 
AT/Auto-reset Perform/Cancel 
AT/AT on startup/Auto-reset Cancel 
AT Perform 
AT on startup Perform 
Auto-reset Perform 
OUT1 proportional band 
 Setting range: 0 to Input span   ( )   
DC voltage, current inputs: 0.0 to 1000.0% 
Integral time 
 Setting range: 0 to 3600 seconds 
Derivative time 
 Setting range: 0 to 1800 seconds 
ARW 
 Setting range: 0 to 100% 
Manual reset 
 Setting range:  Proportional band value 
OUT1 proportional cycle 
 Setting range: 0.5, or 1 to 120 seconds 
OUT1 ON/OFF hysteresis 
 Setting range: 0.1 to 1000.0   ( ) 
DC voltage, current inputs: 1 to 10000 (*1)   
OUT1 high limit 
 Setting range: OUT1 low limit value to 100% 
(Direct current output type: OUT1 low limit value to 105%) 
OUT1 low limit 
 Setting range: 0% to OUT1 high limit value 
(Direct current output type: -5% to OUT1 high limit value) 
OUT1 rate-of-change 
 Setting range: 0 to 100%/second 
OUT2 cooling method 
Air cooling (linear characteristics) 
Oil cooling (1.5th power of the linear characteristics) 
Water cooling (2nd power of the linear characteristics) 
OUT2 proportional band 
 Setting range: 0 to Input span    ( )   
DC voltage, current inputs: 0.0 to 1000.0% 
OUT2 proportional cycle 
 Setting range: 0.5, or 1 to 120 seconds 
OUT2 ON/OFF hysteresis 
 Setting range: 0.1 to 1000.0   ( ),   
DC voltage, current inputs: 1 to 10000 (*1) 
OUT2 high limit 
 Setting range: OUT2 low limit value to 100% 
(Direct current output type: OUT2 low limit value to 105%) 
OUT2 low limit 
 Setting range: 0% to OUT2 high limit value 
(Direct current output type: -5% to OUT2 high limit value) 
(*1) The placement of the decimal point follows the selection. 