User Manual

136
Characters,
Factory Default
Setting Item, Setting Range
and CT2 current
value are alternately
indicated in the PV
Display.
Heater burnout alarm 2 value
Setting range:
20 A: 0.0 to 20.0 A,
100 A: 0.0 to 100.0 A
Loop break alarm time
Setting range: 0 to 200 minutes
Loop break alarm span
Setting range: 0 to 150 ( ), or 0.0 to 150.0 ( )
DC voltage, current inputs: 0 to 1500 (*1)
Event input DI1 allocation
[Event Input Allocation Table]
Event input
function
Input ON
(Closed)
Input OFF
(Open)
No event
Set value memory
Control ON/OFF
Control OFF
Control ON
Direct/Reverse action
Direct action
Reverse action
Preset output 1
ON/OFF
Preset output
Usual control
Preset output 2
ON/OFF
Preset output
Usual control
Auto/Manual control
Manual
control
Automatic
control
Remote/Local
Remote
Local
Program control
RUN/STOP
RUN
STOP
Program control
Holding/Not holding
Holding
Not holding
Program control
Advance function
Advance
function
Usual control
Integral action
Holding
Integral action
Holding
Usual
integral action
Event input DI2 allocation
Selection item: Same as those of Event input DI1 allocation
External setting input high limit
Setting range: External setting input low limit to Input range high limit (*1)
External setting input low limit
Setting range: Input range low limit to External setting input high limit (*1)
Transmission output type
PV transmission
SV transmission
MV transmission
DV transmission
(*1) The placement of the decimal point follows the selection.