Power consumption
100 to 240 V AC
Approx. 8 VA max. (When the maximum number of
options are added: Approx. 11 VA max.)
24 V AC
Approx. 5 VA max. (When the maximum number of
options are added: Approx. 8 VA max.)
24 V DC
Approx. 5 W max. (When the maximum number of
options are added: Approx. 8 W max.)
Rush current
100 to 240 V AC
Max. 14 to 34 A
24 V AC
Max. 34 A
24 V DC
Max. 34 A
Ambient temperature
-10 to 55 (Non-condensing, No icing)
Ambient humidity
35 to 85%RH (Non-condensing)
Weight
BCS2
Approx. 110 g
BCR2
Approx. 160 g
BCD2
Approx. 220 g
Accessories included
Mounting frame 1 piece (BCS2)
Screw type mounting bracket 1 set (BCR2, BCD2)
Instruction manual (excerpt) 1 copy
Accessories sold
separately
Terminal cover
CT (Current transformer):
CTL-6-S-H (For Heater burnout alarm 20 A)
CTL-12-S36-10L1U (For Heater burnout alarm 100 A)
Tool cable CMD-001
Environmental specification
RoHS directive compliant
Attached Functions
Sensor correction
coefficient
Sets slope of input value from a sensor.
Sensor correction
Corrects the input value from the sensor.
Set value lock
Locks the set values to prevent setting errors.
Auto/Manual control
switching
Switches Auto/Manual control.
In Manual control, sets MV with the or key.
SV ramp function
When the SV is adjusted, it approaches the new SV by the preset
rate-of-change. Set SV rise rate and SV fall rate respectively.
SV Rise/Fall rate start type
When control output is turned from OFF to ON, or switched from Manual
to Automatic control, SV start or PV start can be selected for SV rise rate
or fall rate action.
Program control
1 pattern; 9 steps
Power failure
countermeasure
The setting data is backed up in the non-volatile IC memory.
Self-diagnosis
The CPU is monitored by a watchdog timer, and if an abnormal status
occurs, the controller is switched to warm-up status, turning all outputs
OFF.
Automatic cold junction
temperature compensation
This detects the temperature at the connecting terminal between the
thermocouple and the instrument, and always maintains it at the same
status as if the reference junction location temperature was at 0 (32 ).
Indication
range,
Control
range
Thermocouple
[Input range low limit value - 50 (100 )] to
[Input range high limit value + 50 (100 )]
RTD
[Input range low limit value – (Input span x 1%)] to
[Input range high limit value + 50 (100 )]
DC voltage,
Direct current
[Scaling low limit value – (Scaling span x 1%)] to
[Scaling high limit value + Scaling span x 10%]