User Manual
114 
Terminal arrangement 
Refer to ‘Terminal arrangement’. (p.19) 
Console connector 
By  connecting  to  the  tool  cable  (CMD-001,  sold  separately),  the 
following operations can be conducted from an external computer using 
the Console software SWC-BCx01M. 
• Reading and setting of SV, PID and various set values   
• Reading of PV and action status    • Function change 
Setting Structure 
Function 
key 
UP key 
Increases the numeric value. 
By pressing this key for 1 second during Program control, the performing 
step is interrupted, proceeding to the beginning of the next step. 
(Advance function) 
DOWN key 
Decreases the numeric value. 
MODE key 
Selects a setting mode, or registers the set data. 
By pressing this key for 3 seconds during RUN mode, the unit enters 
Monitor mode. 
OUT/OFF key 
The following function can be selected in [OUT/OFF key function]. 
Selection Item 
Action 
Control output OFF function 
Turns the control output ON or OFF. 
Auto/Manual control 
Switches the Auto/Manual control. 
Program control 
Starts/Stops the Program control. 
Indication Performance 
Basic accuracy 
At ambient temperature 23   (for a single unit mounting) 
Thermocouple 
Within  0.2% of each input span 1 digit 
However R, S inputs, 0 to 200   (32 to 392 ): Within  6   (12 ) 
B input, 0 to 300   (0 to 572 ): Accuracy is not guaranteed. 
K, J, E, T, N inputs, Less than 0   (32 ): Within  0.4% of input 
  span 1 digit 
RTD 
Within  0.1% of each input span 1 digit 
Direct current, 
DC voltage 
Within  0.2% of each input span 1 digit 
Effect of ambient temperature 
Within 50 ppm/   of each input span 
Input sampling period 
125 ms 
Time accuracy 
Within  1.0% of setting time 
Control Performance 
Control action 
• PID control (with AT function) 
• PI control: When derivative time is set to 0 
• PD control (with auto-reset, Manual reset function):   
When integral time is set to 0 
• P control (with auto-reset, Manual reset function):   
When derivative and integral times are set to 0. 
• ON/OFF control: When proportional band is set to 0 (or 0.0) 
OUT1 
proportional 
band 
Thermocouple, RTD inputs without decimal point: 0 to Input span 
Thermocouple, RTD inputs with decimal point: 0.0 to Input span 
Direct current, voltage inputs: 0.0 to 1000.0% 
Integral time 
0 to 3600 sec 
Derivative time 
0 to 1800 sec 
OUT1 propor- 
tional cycle 
0.5, or 1 to 120 sec 
ARW 
0 to 100% 










