User Manual

114
Terminal arrangement
Refer to Terminal arrangement. (p.19)
Console connector
By connecting to the tool cable (CMD-001, sold separately), the
following operations can be conducted from an external computer using
the Console software SWC-BCx01M.
Reading and setting of SV, PID and various set values
Reading of PV and action status Function change
Setting Structure
Function
key
UP key
Increases the numeric value.
By pressing this key for 1 second during Program control, the performing
step is interrupted, proceeding to the beginning of the next step.
(Advance function)
DOWN key
Decreases the numeric value.
MODE key
Selects a setting mode, or registers the set data.
By pressing this key for 3 seconds during RUN mode, the unit enters
Monitor mode.
OUT/OFF key
The following function can be selected in [OUT/OFF key function].
Selection Item
Action
Control output OFF function
Turns the control output ON or OFF.
Auto/Manual control
Switches the Auto/Manual control.
Program control
Starts/Stops the Program control.
Indication Performance
Basic accuracy
At ambient temperature 23 (for a single unit mounting)
Thermocouple
Within 0.2% of each input span 1 digit
However R, S inputs, 0 to 200 (32 to 392 ): Within 6 (12 )
B input, 0 to 300 (0 to 572 ): Accuracy is not guaranteed.
K, J, E, T, N inputs, Less than 0 (32 ): Within 0.4% of input
span 1 digit
RTD
Within 0.1% of each input span 1 digit
Direct current,
DC voltage
Within 0.2% of each input span 1 digit
Effect of ambient temperature
Within 50 ppm/ of each input span
Input sampling period
125 ms
Time accuracy
Within 1.0% of setting time
Control Performance
Control action
PID control (with AT function)
PI control: When derivative time is set to 0
PD control (with auto-reset, Manual reset function):
When integral time is set to 0
P control (with auto-reset, Manual reset function):
When derivative and integral times are set to 0.
ON/OFF control: When proportional band is set to 0 (or 0.0)
OUT1
proportional
band
Thermocouple, RTD inputs without decimal point: 0 to Input span
Thermocouple, RTD inputs with decimal point: 0.0 to Input span
Direct current, voltage inputs: 0.0 to 1000.0%
Integral time
0 to 3600 sec
Derivative time
0 to 1800 sec
OUT1 propor-
tional cycle
0.5, or 1 to 120 sec
ARW
0 to 100%