User Manual
113 
General Structure 
External 
dimensions 
BCS2 
48 x 48 x 68 mm (W x H x D) (Depth of control panel interior: 60) 
BCR2 
48 x 96 x 68 mm (W x H x D) (Depth of control panel interior: 60) 
BCD2 
96 x 96 x 68 mm (W x H x D) (Depth of control panel interior: 60) 
Mounting 
Flush 
Case 
Flame-resistant resin, Black 
Front panel 
Membrane sheet 
Drip-proof/Dust-proof 
Front panel: IP66,    Rear case: IP20,    Terminal section: IP00 
Standards 
EN 
EN61010-1 (Pollution degree 2, Overvoltage category  ) 
Indication 
structure 
PV Display 
Indicates PV. 
7-segment Red LED display 
BCS2 
Character size: 12.4 x 5.8 mm (H x W) 
BCR2 
Character size: 14 x 5.8 mm (H x W) 
BCD2 
Character size: 24 x 11 mm (H x W) 
SV Display 
Indicates SV. 
7-segment Green LED display 
BCS2 
Character size: 8.8 x 3.9 mm (H x W) 
BCR2 
Character size: 14 x 5.8 mm (H x W) 
BCD2 
Character size: 14 x 7 mm (H x W) 
MEMO/STEP 
Display 
(BCR2, 
BCD2) 
Indicates Set value memory number (Fixed value control) or Step 
number (Program control). 
7-segment Green LED display 
BCR2 
Character size: 14 x 5.8 mm (H x W) 
BCD2 
Character size: 14 x 7 mm (H x W) 
Action 
indicators 
O1 (Green) 
Lit when control output OUT1 is ON. 
For direct current output type, flashes corresponding 
to the MV in 125 ms cycles. 
O2 (Yellow) 
Lit when control output OUT2 (EV2, DS, DA options) is 
ON.   
For direct current output type (DA option), flashes   
corresponding to the MV in 125 ms cycles. 
EV1 (Red) 
Lit when Event output 1 is ON. 
EV2 (Red) 
Lit when Event output 2 (EV2 option) is ON. 
Unlit if    (Heating/Cooling control relay contact 
output) is selected in [Event output EV2 allocation]. 
AT (Yellow) 
Flashes while AT, ‘AT on startup’ or Auto-reset is 
performing. 
R/L (Yellow) 
Lit during Remote action from Remote/Local 
switching (EIT option). 
T/R (Yellow) 
Lit during Serial communication (C5W, C5 options) TX 
(transmitting) output. 
MEMO 
(Yellow) 
Lit when Set value memory number (Fixed value   
control) is indicated. 
(BCR2, BCD2) 
STEP 
(Green) 
Lit when a step number (Program control) is indicated. 
(BCR2, BCD2) 