User Manual

102
9.5 Using as a Converter
This instrument can be used as a simplified converter.
Converts each input value (thermocouple, RTD, DC voltage and current inputs) to 4 to 20 mA DC,
and outputs it.
When OUT1 is Direct current output, the controller can be used as a converter.
Select Converter in [Controller/Converter] in Engineering mode.
Factory default value is Controller.
When this instrument is switched from controller to converter, values in the table below (Table 9.5-1)
are automatically set. The SV Display indicates nothing.
When this instrument is switched from converter to controller, the PV Display indicates for
1 second, and factory default values are set.
(Table 9.5-1)
Setting Item
Set Value (or Selection)
SV1 (*)
Scaling low limit value
SV2 (*)
(BCS2: EIW, EIT, EI options,
BCR2/BCD2: C5W, EIW, EIT, EI options)
Scaling low limit value
SV3 (*)
(BCS2: EIW, EI options,
BCR2/BCD2: C5W, EIW, EIT, EI options)
Scaling low limit value
SV4 (*)
(BCS2: EIW, EI options,
BCR2/BCD2: C5W, EIW, EIT, EI options)
Scaling low limit value
OUT1 proportional band (*)
Input span
Integral time
0
Derivative time
0
Reset
0 (Reset value, calculated by Auto-reset function)
OUT2 proportional band (*)
Input span
EV1/EV2 alarm value 0 Enabled/Disabled
Disabled
EV1/EV2 alarm value
0 or Input range low limit value (Scaling low limit
value)
EV1/EV2 high limit alarm value
0 or Input range low limit value (Scaling low limit
value)
EV1/EV2 alarm hysteresis
1.0
EV1/EV2 alarm delay time
0
EV1/EV2 alarm Energized/De-energized
Energized
Loop break alarm time
0
Loop break alarm span
0
Direct/Reverse action
Direct action
OUT/OFF key function
Control output OFF function
Event input DI1 allocation
(BCS2: EIW, EIT, EI options,
BCR2/BCD2: C5W, EIW, EIT, EI options)
No event
Event input DI2 allocation
(BCS2: EIW, EI options,
BCR2/BCD2: C5W, EIW, EIT, EI options)
No event
Event output EV1 allocation
No event
Event output EV2 allocation
(EV2 option)
No event