Setting Item, Function, Setting Range
EV2 alarm Energized/De-energized
• Selects Energized/De-energized status for EV2 alarm.
(Refer to ‘EV1/EV2 Energized/De-energized’ on p.50.)
• Selection item:
Energized
De-energized
Available when any alarm from (Alarm output, High limit alarm) to (Alarm output, High/Low
limits with standby independent alarm) is selected in [Event output EV2 allocation].
TS2 output step number
• Sets the step number at which Time signal output TS2 will be turned OFF or ON
during Program control.
(Refer to ‘Time Signal Output’ on p.52.)
• Setting range: 1 to 9
Available only when (Time signal output) is selected in [Event output EV2 allocation].
TS2 OFF time
• Sets Time signal output TS2 OFF time.
(Refer to ‘Time Signal Output’ on p.52.)
• Setting range: 00:00 to 99:59 (*4)
Available only when (Time signal output) is selected in [Event output EV2 allocation].
TS2 ON time
• Sets Time signal output TS2 ON time.
(Refer to ‘Time Signal Output’ on p.52.)
• Setting range: 00:00 to 99:59 (*4)
Available only when (Time signal output) is selected in [Event output EV2 allocation].
and CT1 current
value are alternately
indicated in the PV
Display.
Heater burnout alarm 1 value
• Sets the heater current value for Heater burnout alarm 1.
Characters and CT1 current value are alternately indicated in the PV Display.
When OUT1 is ON, the CT1 current value is updated.
When OUT1 is OFF, the unit memorizes the previous value when OUT1 was ON.
Upon returning to set limits, the alarm will stop.
• Setting range:
20 A: 0.0 to 20.0 A
100 A: 0.0 to 100.0 A
Setting to 0.0 disables the alarm.
Not available for the Direct current output type.
Available when Heater burnout alarm (C5W, EIW, W options) is ordered.
(*4) Time unit follows the selection from [Step time unit].