User Manual
114
Terminal arrangement
Refer to ‘Terminal arrangement’. (p.19)
Console connector
By connecting to the tool cable (CMD-001, sold separately), the
following operations can be conducted from an external computer using
the Console software SWC-BCx01M.
• Reading and setting of SV, PID and various set values
• Reading of PV and action status • Function change
Setting Structure
Function
key
UP key
Increases the numeric value.
By pressing this key for 1 second during Program control, the performing
step is interrupted, proceeding to the beginning of the next step.
(Advance function)
DOWN key
Decreases the numeric value.
MODE key
Selects a setting mode, or registers the set data.
By pressing this key for 3 seconds during RUN mode, the unit enters
Monitor mode.
OUT/OFF key
The following function can be selected in [OUT/OFF key function].
Selection Item
Action
Control output OFF function
Turns the control output ON or OFF.
Auto/Manual control
Switches the Auto/Manual control.
Program control
Starts/Stops the Program control.
Indication Performance
Basic accuracy
At ambient temperature 23 (for a single unit mounting)
Thermocouple
Within 0.2% of each input span 1 digit
However R, S inputs, 0 to 200 (32 to 392 ): Within 6 (12 )
B input, 0 to 300 (0 to 572 ): Accuracy is not guaranteed.
K, J, E, T, N inputs, Less than 0 (32 ): Within 0.4% of input
span 1 digit
RTD
Within 0.1% of each input span 1 digit
Direct current,
DC voltage
Within 0.2% of each input span 1 digit
Effect of ambient temperature
Within 50 ppm/ of each input span
Input sampling period
125 ms
Time accuracy
Within 1.0% of setting time
Control Performance
Control action
• PID control (with AT function)
• PI control: When derivative time is set to 0
• PD control (with auto-reset, Manual reset function):
When integral time is set to 0
• P control (with auto-reset, Manual reset function):
When derivative and integral times are set to 0.
• ON/OFF control: When proportional band is set to 0 (or 0.0)
OUT1
proportional
band
Thermocouple, RTD inputs without decimal point: 0 to Input span
Thermocouple, RTD inputs with decimal point: 0.0 to Input span
Direct current, voltage inputs: 0.0 to 1000.0%
Integral time
0 to 3600 sec
Derivative time
0 to 1800 sec
OUT1 propor-
tional cycle
0.5, or 1 to 120 sec
ARW
0 to 100%