User Manual
108
High limit with standby alarm
OFF
ON
SV SV
OFF
ON
OFF
ON
OFF
ON
SV
Low limit with standby alarm
High/Low limits with standby alarm
H/L limits with standby independent alarm
Alarm
action
Alarm
output
Alarm
action
Alarm
output
SV
+ side
- side
+ side
- side
-EV1 value
-EV1 value
+EV1 value
+EV1 value
EV1 hysteresis
EV1 hysteresis
EV1 hysteresis
EV1 hysteresis
EV1 value EV1 value
EV1 low limit value
EV1 high limit value
• EV1 value, EV1 high limit value, and EV1 hysteresis represent EV1 alarm value,
EV1 high limit alarm value and EV1 alarm hysteresis respectively.
For EV2, read “EV2” for “EV1”.
• EV1 indicator lights when Event output 1 terminals 3 and 4 are ON, and
goes off when their output terminals 3 and 4 are OFF.
EVT2 indicator lights when Event output 2 terminals 5 and 6 are ON, and
goes off when their output terminals 5 and 6 are OFF.
• BCR2, BCD2: Event output 1 terminal numbers: 17, 18
Event output 2 terminal numbers: 19, 20
: Event output 1 terminals 3 and 4: ON (closed).
: Event output 1 terminals 3 and 4: ON (closed) or OFF (open).
: Event output 1 terminals 3 and 4: OFF (open).
: Alarm output is in Standby.