9.5 Using as a Converter
This instrument can be used as a simplified converter.
Converts each input value (thermocouple, RTD, DC voltage and current inputs) to ‘4 to 20 mA DC’,
and outputs it.
When OUT1 is Direct current output, the controller can be used as a converter.
Select ‘Converter’ in [Controller/Converter] in Engineering mode.
Factory default value is Controller.
When this instrument is switched from controller to converter, values in the table below (Table 9.5-1)
are automatically set. The SV Display indicates nothing.
When this instrument is switched from converter to controller, the PV Display indicates for
1 second, and factory default values are set.
(Table 9.5-1)
Setting Item
Set Value (or Selection)
SV1 (*)
Scaling low limit value
SV2 (*)
(BCS2: EIW, EIT, EI options,
BCR2/BCD2: C5W, EIW, EIT, EI options)
Scaling low limit value
SV3 (*)
(BCS2: EIW, EI options,
BCR2/BCD2: C5W, EIW, EIT, EI options)
Scaling low limit value
SV4 (*)
(BCS2: EIW, EI options,
BCR2/BCD2: C5W, EIW, EIT, EI options)
Scaling low limit value
OUT1 proportional band (*)
Input span
Integral time
0
Derivative time
0
Reset
0 (Reset value, calculated by Auto-reset function)
OUT2 proportional band (*)
Input span
EV1/EV2 alarm value 0 Enabled/Disabled
Disabled
EV1/EV2 alarm value
0 or Input range low limit value (Scaling low limit
value)
EV1/EV2 high limit alarm value
0 or Input range low limit value (Scaling low limit
value)
EV1/EV2 alarm hysteresis
1.0
EV1/EV2 alarm delay time
0
EV1/EV2 alarm Energized/De-energized
Energized
Loop break alarm time
0
Loop break alarm span
0
Direct/Reverse action
Direct action
OUT/OFF key function
Control output OFF function
Event input DI1 allocation
(BCS2: EIW, EIT, EI options,
BCR2/BCD2: C5W, EIW, EIT, EI options)
No event
Event input DI2 allocation
(BCS2: EIW, EI options,
BCR2/BCD2: C5W, EIW, EIT, EI options)
No event
Event output EV1 allocation
No event
Event output EV2 allocation
(EV2 option)
No event