8. Specifications
Supply voltage 100 to 240V AC 50/60Hz
Allowable voltage
fluctuation
85 to 264V AC
Thermocouple : Within 0.3% of each input span 1digit,
Less than 0 (32 ): Within 0.4% of each input span 1digit
Accuracy
(Setting, Indication)
RTD : Within 0.2% of input span 1digit
Input sampling
period
0.5 sec
Relay contact: 1a Control capacity: 3A 250V AC (resistive load)
1A 250V AC (inductive load cos =0.4)
Electrical life : 100,000 cycles
Control output
(OUT)
Non-contact voltage (for SSR drive): 10
+3
0
V DC (Max. 20mA DC)
Short circuit protected
Circuit insulation
configuration
*1: For Relay contact output, Input is electrically insulated from Output.
*2: For Non-contact voltage output, Input is not electrically insulated from Output.
Insulation
resistance
10M or more, at 500V DC
Dielectric strength Between input terminal and power terminal : 1.5kV AC for 1 minute
Between output terminal and power terminal: 1.5kV AC for 1 minute
Power
consumption
Approx. 7VA
Ambient
temperature
0 to 50 (32 to 122 )
Ambient humidity 35 to 85%RH (No icing, Non-condensing)
Weight Approx. 120g
Accessories
included
Mounting frame 1 piece
Instruction manual 1 copy
Accessories
sold separately
Terminal cover
2 Alarm outputs Relay contact: 1a Control capacity: 3A 250V AC (resistive load),
Electrical life : 100,000 cycles
If you have any inquiries, please consult our agency or the vendor where you purchased the unit.
SHINKO TECHNOS CO., LTD.
OVERSEAS DIVISION
:
:
:
Reg. Office
URL
E-mail
2-5-1, Senbahigashi, Minoo, Osaka, Japan
http://www.shinko-technos.co.jp
overseas@shinko-technos.co.jp
Tel :
Fax:
+81-72-727-6100
+81-72-727-7006