User Manual

2
2. Name and functions of sections
[Displays, Indicators]
PV display (Red) : Indicates the PV (process variable) or setting characters in any setting mode.
SV display (Green) Indicates the SV (desired value), output MV (manipulated variable) or each set
value in any setting mode.
OUT indicator (Green): Lights when control output (OUT) is ON.
EV1 indicator (Red) : Lights when Alarm 1 (A1) output (option) is ON.
EV2 indicator (Red) : Lights when Alarm 2 (A2) output (option) is ON.
AT indicator (Yellow) : Flashes while auto-tuning (AT) or auto-reset is performing.
[Keys]
Increase Key ( ) : Increases the numeric value or makes a selection.
Decrease Key ( ) : Decreases the numeric value or makes a selection.
Mode Key ( ) : Switches the setting mode, or registers the set (or selected) value.
[By pressing the Mode Key, the set (or selected) value can be registered.]
3. Mounting to the control panel
3.1 Site selection
Caution
Use within the following temperature and humidity ranges.
Temperature: 0 to 50 (32 to 122 ), Humidity: 35 to 85%RH (No icing, non-condensing)
If the BCS1 is installed through the face of a control panel, the ambient temperature of the BCS1 must be
kept to under 50 . Otherwise, the life-span of electronic parts (especially electrolytic capacitors) of the
BCS1 will be shortened.
This instrument is intended to be used under the following environmental conditions (IEC61010-1):
Overvoltage category , Pollution degree 2
Ensure the mounting location corresponds to the following conditions:
A minimum of dust, and an absence of corrosive gases
No flammable, explosive gases
Few mechanical vibrations or shocks
No exposure to direct sunlight, an ambient temperature of 0 to 50 (32 to 122 ) that does not change
rapidly, and no icing
An ambient non-condensing humidity of 35 to 85%RH
No large capacity electromagnetic switches or cables through which large current is flowing
No water, oil or chemicals or where the vapors of these substances can come into direct contact with
the controller
(Fig. 2-1)
Action indicators
Increase Key
Decrease Key
Mode Key
SV display
PV display