ON/OFF:Turn on/off button, operate this button (press for 5s) to turn on/off the unit;
↑:The up key, add to the set value or select the last record/menu;
↓:The down key, lower the set value or select the next record/menu;
←:The left key, select the previous bit of data;
→:The right key, select the latter data;
ENTER:Enter, confirm Entry;
ESC:Escape, go back to the previous menu;
After starting up, in any interface, if there is no keyboard operation for 60 seconds, it will automatically
return to the normal display interface.
After the air conditioner powered on, press any key and the backlight will be on. If there is no keyboard
operation for 60 seconds, the backlight will be off.
The default operation password of the air conditioner is "0001", press ‘enter key’ to enter the password
into the normal display interface, press left shift key and right shift key to select the bit need to be entered,
press up and down key to modify, press enter key to confirm after input. If the password is not correct, the
interface will display an error message and cannot change the settings. If the password is correct, go to the
main menu and edit the settings.
Refrigeration Operation Control
When the temperature reaches refrigeration control point, the air conditioner will run large cooling output.
When the temperature in the kiosk cabinet is less than the refrigeration control point, the refrigeration stops
running.
Parameter Default The Set Range Unit Set Point Description
Refrigeration control point
22
10~50
℃
Air-conditioner Refrigeration
Control Temperature Point
Refrigeration sensitivity 4
1~10
℃
Sensitivity of Temperature
Control
Heating Operation (Optional)
Heating start point = heating stop point - heating sensitivity. When the internal temperature in the kiosk
cabinet is lower than the heating start point, heating operation will start; when the internal temperature in the
kiosk cabinet is higher than the heating stop point, heating will stop.