Table 6-5 Acce&Dece time terminal selection logic mode
Can realize selection for Acce&Dece time1~7 by ON/OFF combination of
Acce&Dece time terminal.
10: external equipment fault input. Can input fault signal of external
equipment by this terminal to be convenient for the inverter to monitor fault of
external equipment. The inverter displays “E0.14”, namely external equipment
fault alarm after receiving the external equipment fault signal.
11: exterior restoration input.
After the fault alarm takes place in the
inverter, can restore the inverter through this terminal. Its function is same as
function of key on the operation panel.
12: free stop input. This function is same as free stop during running
defined in F1.05,but it’s realized by control terminal to be convenient for
long-distance control.
13: exterior stop command. This command is effective to all run
command channel,when this function is effective the inverter stops running in
mode set by F1.05.
14: DC injection braking input command DB during stop. Implement
DC injection braking to the motor during stop by control terminal,in order to
realize urgent parking and accurate orientation of the motor. Braking initial
frequency, braking time are defined in F1.06, F1.07.
15: inverter run forbiddance. The inverter during running stops freely
when this terminal is effective and forbidden to start in waiting status. Mainly
applied to occasion needing safe linkage.
16~17: frequency increasing control UP/descending control DOWN.
Realize frequency increasing or descending by control terminal, which substitute
for keypad to realize long-distance control. Effective during common run if
F0.00=2.Increasing descending speed is set by F5.09.
Terminal 2 Ter minal 2 Terminal 1 Acce/Dece time selection
OFF OFF OFF Acce time 1/ Dece time 1
OFF OFF ON Acce time 2/ Dece time 2
OFF ON OFF Acce time 3/ Dece time 3
OFF ON ON Acce time 4/ Dece time 4
ON OFF OFF Acce time 5/ Dece time 5
ON OFF ON Acce time 6/ Dece time 6
ON ON OFF Acce time 7/ Dece time 7
RESET