www.enc.net.cn/en Tel/Fax:86-755-26984485/26985120 6 Detailed function description
85
3: consecutive circulation. As shown in Fig.6-24the inverter start next
circle automatically after finishing a circleuntil there is stop command.
LED 2
nd
bit:
0: start from first step. Stop during running caused by stop command,
failure or power offafter restarting the inverter will run from first step.
1: continue to run from step frequency of interruption moment. When
stop during running caused by stop command or failurethe inverter will record
current step used time automatically and enter into this step automatically after
restartingcontinue to run for residual time according to defined frequency of this
step, as shown in Fig.6-25. The inverter will rerun from first step after restarting if
power off.
Fig.6-25 PLC starting mode 1
LED 3
rd
bit : PLC run time unit
0: second1: minute
This unit is only effective to PLC run step timefor accelerating decelerating
time of PLC run period, their unit selection is determined by F0.07.
LED 4
th
bit
0: power off no memory
1: the inverter still in the memory running state when the power off, it needs
renew run (terminal control exceptional) when power on without automotive start.
Make memory of the simple PLC running segments, speed and running time
before power off. Automotive read the state of the power off when restart, but the
inverter doesn’t run directly, (control commands except for the terminal mode),
output freq.Hz
Interruption signal
a
1
: step 1 accelerating time a
2
: step 2 accelerating time
a
3
: step 3 accelerating time d
2
: step 2 decelerating time
f
1
: step 1 frequency f
2
: step 2 frequency
f
3
: step 3 frequency
a
1
f
1
d
2
a
2
f
2
a
3
f
3
Step 1
Step 2
Used time
Step 2 residual time
Time t