Service manual

www.enc.net.cn/en Tel/Fax:86-755-26984485/26985120 6 Detailed function description
80
14: exterior pulse input
F3.29
YCI run-in delay time Range: 0.0999.9s 0.0
PID feedback signal loss
detection
Range: 0.0999.9s 0.0
YCI input delay time: the inverter first run at RS485 set frequency after start-up
and change set frequency to RS485+YCI after delay time passed.
PID feedback signal loss detection: When F3.29=0.0, PID feedback signal loss
detection protection function invalid, when F3.290, feedback signal<12.5%
given value and the constant timeF3.29, then you can judge the feedback signal
loss, avoid damaging the equipment. Fault code is displayed as E017.
F3.30
Failure relay TATBTC
function selection
Range: 0~24 15
Table 6-2 Failure relay TATBTC function selection
Item Corresponding function Item Corresponding function
0 Inverter running signal (RUN) 1 Frequency arriving signal (FAR)
2
Frequency level detecting
signal (FDT1)
3 Reserved
4 Overload warning signal(OL) 5 Output Freq. reach high limit(FHL)
6 Output Freq. reach low limit(FLL) 7
Inverter stop for under voltage
blockage (LU)
8 Stop for exterior failure(EXT) 9 Inverter zero rotate speed running
10 PLC running 11 Simple PLC segment run finished
12 PLC finish one cycle run 13 Reserved
14 Inverter ready to run(RDY) 15 Inverter failure
16 traverse high and low limit restriction 17 Interior counter final value arrive
18
Interior counter specified value
arrive
19 Set runtime arrive
20 Interior timer timing arrive 21 Multifunctional input terminal signal input
22 FWD running 23 REV running
24 Reserved