Service manual
www.enc.net.cn/en Tel/Fax:86-755-26984485/26985120 6 Detailed function description
72
F2.37
Multi-step freq. 8
Range: Lower limit freq.-
u
pp
er limit fre
q
.
10.00Hz
VF frequency value 0 Range:0.00-F2.39 10.00Hz
F2.38
Multi-step freq. 9
Range: Lower limit freq.-
u
pp
er limit fre
q
.
20.00Hz
VF voltage value 0
Range:0.00-F2.40
20.00%
F2.39
Multi-step freq. 10
Range: Lower limit freq.-
u
pp
er limit fre
q
.
20.00Hz
VF frequency value 1 Range:F2.37-F2.41 20.00Hz
F2.40
Multi-step freq. 11
Range: Lower limit freq.-
u
pp
er limit fre
q
.
40.00Hz
VF voltage value 1 Range:F2.38-F2.42 40.00%
F2.41
Multi-step freq. 12
Range: Lower limit freq.-
u
pp
er limit fre
q
.
25.00Hz
VF frequency value 2 Range:F2.39-F2.43 25.00Hz
F2.42
Multi-step freq. 13
Range: Lower limit freq.-
u
pp
er limit fre
q
.
50.00Hz
VF voltage value 2 Range:F2.40-F2.44 50.00%
F2.43
Multi-step freq. 14
Range: Lower limit freq.-
u
pp
er limit fre
q
.
40.00Hz
VF frequency value 3 Range:F2.41- high limit freq. 40.00Hz
F2.44
Multi-step freq. 15
Range: Lower limit freq.-
u
pp
er limit fre
q
.
80.00Hz
VF voltage value 3
Range:F2.42-100.0%(rated
volta
g
e
)
80.00%
These parameters are compound, two kinds of function
can’t be used
simultaneously, for details please check below:
When F0.15=4, F2.37~F2.44 are for V/F curve setting, for detailed function
description, please see that for F0.15.
When F0.15≠4, F2.37~F2.44 are used for multi-section frequency. Setting
mode and function are the same as F2.30.
F2.45
Jumping freq. 1
Range: 0.00-400.00Hz
0.00Hz
F2.46
Jumping freq. 1 range
Range: 0.00-30.00Hz
0.00Hz
F2.47 Reserved
F2.48 Reserved
F2.49 Reserved
F2.50 Reserved
F2.45, F2.46 function is set for keeping inverter output frequency away from