F2.12 LED display control 2 Range: 00001111 1111
F2.12 make use of 4 bit of the parameter to set if C-11—C-14 is displayed in
parameter, thereinto 0 indicates not displayed, 1 indicates displayed. Set
parameter of 4 bit is as following figure:
F2.13
Parameter operation
control
Range: LED 1
st
bit: 0~2
LED 2
nd
bit: 0~2
LED 3
rd
bit: 0~4
000
LED 1
st
bit
0: all parameter allowed to be modified
1: except this parameterall other parameter not allowed to be changed
2: except F0.01 and this parameterall other parameter not allowed to
be changed
LED 2
nd
bit
0: no action
1: renew factory default
2: clear history failure record
LED 3
rd
bit
0: lock all buttons
1: all buttons locked except STOP key
2: all buttons locked except , STOP key
3: all buttons locked except RUN, STOP key
4: all buttons locked except SHIFT, STOP key
C-11: analog input VCI
C-12: analog input YCI
C-13: analog input CCI
C-14: outer pulse input
4
th
bit 3
rd
bit 2
nd
bit 1
st
bit
(1) Factory default of this function parameter is 0i.e., all the function parameter can be
modified. After modifying the parameter, please first set this function code to 0 if you
want to modify function code setting. After modifying the parameter you can change this
function code setting to expected protection grade if parameter protection is needed.
(2) After clearing memory information or renewing manufacturer parameter, the 1st bit of
this function code will resume 0 automatically.
(3) After the 3rd bit of F2.13 is setted, the keypad will be locked after you press ESC for
5seconds, and then corresponding keys is locked. Please press ESC for 5 seconds again
for unlocking the keypad.
note