F2.08 Jog Dece time Range: 0.160.0S 20.0S
Jog frequency has the highest priority. Under any status, the inverter
would transit to run at jog frequency at once according to set jog accelerating,
decelerating time as long as jog command is inputted, as shown in Fig.6-11.
Jog accelerating time means time during which the inverter accelerate from
0Hz to high limit frequencyJog Dec time means time during which the inverter
decelerate from high limit frequency to 0Hz.
F2.09
Freq. input channel
combination
Range: 028 0
0: VCICCI
1: VCICCI
2: YCICCI
YCI specified frequency is positive or negative. Here YCI input 0~+10V
corresponds to frequency -50.00Hz~+50.00Hz0~5V corresponds to frequency
-50.000Hz5~10V corresponds to 0~+50.00Hz.
3: RS485+YCI
When you choose RS485+YCIYCI input voltage 0~5V—YCI dead band
(F7.12) corresponds to -50.00Hz—0.00Hz5V—YCI dead band (F7.12)YCI
5V+YCI dead band (F7.12) corresponds to 0HzYCI>5V+YCI dead band (F7.12)
corresponds to 0.00~+50.00Hz. You can carry out tension control by this function.
4: VCIYCI
5: reserved
6: external pulse provisionCCI
7: external pulse provisionCCI
8: reserved
Fi
g
.6-11
j
o
g
run
Jog
freq.
Jog
accelerating
time
Jog decelerating
time
Jog
signal
Jog
freq.
Jog
signal
(1) Keypad, control terminal and serial port can do jog control all.
(2) The inverter will stop according to Dec stop mode after jog run command is withdrawn.
note