Service manual

www.enc.net.cn/en Tel/Fax:86-755-26984485/26985120 6 Detailed function description
60
This function determines Acce/Dece time unit.
0: second
1: minute
F0.08 Acce time 1 Range: 0.16000.0 20.0
F0.09 Dece time 1 Range: 0.16000.0 20.0
Accelerating time is defined as time for inverter accelerating from 0Hz to high
limit frequencysee t1 in Fig.6-3Dece time is defined as time for inverter
decelerating from high limit frequency to 0Hz, see t2 in Fig.6-3.
Fig.6-3 Acce/Dece time definition
F0.10 Upper limit freq. Range: lower limit freq.400.00Hz 50.00Hz
F0.11 lower limit freq. Range: 0.00upper limit freq. 0.00Hz
F0.12
Lower limit freq.
run mode
Range: 0:run at lower limit freq.
1: stop by slow down
2: Free stop
0
The inverter will decrease output frequency gradually in set decelerating time
when actual set frequency is lower than low limit frequencyafter reaching low
limit frequencythe inverter will run at low limit frequency if low limit frequency
running mode set to 0The inverter will reduce output frequency sequentially to
zero frequency run if low limit frequency running mode set to 1; If the lower limit
frequency operation mode selected to be 2 then motor stops freely. The inverter
t
1
t
2
time
Output freq.
high limit frequency
note
(1) This function is effective for all Acce/Dece process except for jog run.
(2) To choose second as time unit is recommended.
note
(1) In EDS1000 series inverter 7 kinds of Acce/Dece time are defined in totalhere we
only define Acce/Dece time 1Acc/Dec time 2~7 are defined in F2.18~F2.29
please refer to Section 6.3.
(2) Can choose time unit minute or second for Acce/Dece time 1~7 by F0.07, factory
default is second.