Service manual
www.enc.net.cn/en Tel/Fax:86-755-26984485/26985120 6 Detailed function description
59
F0.04
Acce/Dece mode
selection
Range: 0, 1 0
0: linear Acce/Dece mode. Output frequency increases or decreases
according to constant slope, just as shown in Fig.6-1.
1: S curve Acce/Dece mode. Output frequency increases or decreases
according to S curve, just as shown in Fig.6-2.
Fig.6-1 linear Acce/Dece Fig.6-2 S curve Acce/Dece
F0.05
S curve starting time
Range: 10.0(%)-50.0(%)
(Acce/Dece time)F0.05+ F0.06
≤90(%)
20.0(%)
F0.06
S curve rising time
Range: 10.0(%)-70.0(%)
(Acce/Dece time)F0.05+ F0.06
≤90(%)
60.0(%)
F0.05, F0.06 is only effective when S curve Acce/Dece mode(F0.04=1)is
selected during Acc/Dec selection, and F0.05 ,F0.06≤90%.
S curve starting time is shown as Fig. 6-2③,slope of output frequency variation
increases by degrees from 0.
S curve rising time is shown as Fig.6-2②,slope of output frequency variation is
constant.
S curve ending time is shown as Fig.6-2①,slope of output frequency variation
steps down to 0.
F0.07 Acce/Dece time unit Range: 0, 1 0
t
1
t
2
time
Freq.
50.00Hz
50.00Hz
Freq.
t
1
t
2
③
②
①
①
②
③
time
If the 2
nd
bit is set to“1”,this function is effective for keypad run command
channel, terminal run command channel and serial port run command channel.
note
S curve Acce/Dece mode,suitable for starting and stopping elevator, deferent belt,
carrier transporter load etc..
note