Service manual
www.enc.net.cn/en Tel/Fax:86-755-26984485/26985120 6 Detailed function description
58
F0.01 Freq. digit setting
Range: Lower limit freq.-
u
pp
er limit fre
q
.
50.00Hz
F0.01 parameter is original set frequency of the inverter when frequency setting
channel is defined as number setting (F0.00=1, 3).
F0.02
Run command
channel selection
Range: 0~4 0
0: keypad run control. Start and stop the inverter by , ,
key on the keypad.
1: terminal run command control (keypad STOP command ineffective).
Start and stop the inverter by exterior control terminal FWD, REV, X1~X8 etc..
2: terminal run command control (keypad STOP command effective).
Start and stop the inverter by exterior control terminal FWD, REV, X1~X8 etc..
3: serial port run command control (keypad STOP command ineffective).
Start and stop the inverter by RS485 interface.
4: serial port run command control (keypad STOP command effective).
Start and stop the inverter by RS485 interface.
F0.03 Run direction setting
Range: LED 1
st
bit: 0,1
LED 2
nd
bit: 0,1
LED 3
rd
bit: 0,1
100
The 1
st
bit:
0: forward run
1: reserved
The 2
nd
bit:
0: reverse run allowed
1: reverse run banned. The inverter will stop output when there is reverse
run command.
The 3
rd
bit:
REV/JOG key selection
0: as reverse run key
1: as jog key
Relation between frequency and input information is determined by function code
F7.00~F7.17 when frequency input channel is 4, 5, 6, 7,please see Section 6.8.
note
RUN
STOP
REV
JOG
!
The inverter can change run command channel by modifying F0.02 during waiting and
running,please confirm that modification is allowed during running on the spot.