www.enc.net.cn/en Tel/Fax:86-755-26984485/26985120 5 Function parameter schedule graph
54
F7.13 PULSE max. input pulse 0.120.0K 0.1K 10.0K
F7.14 PULSE min. provision
0.0F7.16(PULSE max.
provision)
0.01K 0.0K
F7.15
PULSE min. provision corresponding
freq.
0.00high limit frequency 0.01Hz 0.00Hz
F7.16 PULSE max. provision
F7.14 (PULSE min. provision)
F7.13 (max. input pulse)
0.1K 10.0K
F7.17
PULSE max. provision corresponding
freq.
0.00high limit frequency 0.01 Hz 50.00 Hz
F8Motor and vector control parameter group
Function
code
Name Set range
Min.
unit
Factory
defaul
t
Modifi
-cation
F8.00 Control mode setting
0: V/F control
1: vector control
remark: for EDS1300 it can’t be 1
1 0 ×
F8.01 Motor rated voltage 1480V 1V
Depend on
device type
×
F8.02 Motor rated current 0.1999.9A 0.1A
Depend on
device type
×
F8.03 Motor rated frequency 1.00400.00Hz 0.01 Hz
Depend on
device type
×
F8.04 Motor rated speed 19999r/min 1r/min
Depend on
device type
×
F8.05 Motor pole quantity 214 2
Depend on
device type
×
F8.06 Motor rated power 0.1999.9KW 0.1
Depend on
device type
×
F8.07 Motor stator resistance 0.0009.9999ohm 0.001 ohm
Depend on
device type
×
F8.08 Motor rotor resistance 0.0009.9999ohm 0.001 ohm
Depend on
device type
×
F8.09 Motor stator leakage inductance 0.0999.9mH 0.1 mH
Depend on
device type
×
F8.10 Motor rotor leakage inductance 0.0999.9mH 0.1 mH
Depend on
device type
×
F8.11 Motor mutual inductance 0.0999.9mH 0.1 mH
Depend on
device type
×
F8.12 Torque limit 50.0200.0%(rated current) 0.1% 150.0% ×
F8.13 Speed loop proportion gain 0.0006.000 0.001 0.700 ×
F8.14 Speed loop integral time constant 0.0009.999 0.001 0.360 ×
F8.15 Motor stability coefficient 04 3 ×
F8.16 Filter time displayed instead freq. 0~999 1 6 ×
F8.17 Motor speed correction factor 09999% 0 100% ×
F9Protection function parameter group
Function
code
Name Set range
Min.
unit
Factory
default
Modifi
-cation
F9.00
W
aiting time for
starting again when
p
ower off
0.020.0S (0 means do not enable this
function)
0.1S 0 ×
F9.01
Failure self-renew
times
010
0 shows no automatic reset function
Note:no automatic reset function when over
1 0 ×