Service manual
www.enc.net.cn/en Tel/Fax:86-755-26984485/26985120 5 Function parameter schedule graph
54
F7.13 PULSE max. input pulse 0.1-20.0K 0.1K 10.0K ○
F7.14 PULSE min. provision
0.0-F7.16(PULSE max.
provision)
0.01K 0.0K ○
F7.15
PULSE min. provision corresponding
freq.
0.00-high limit frequency 0.01Hz 0.00Hz ○
F7.16 PULSE max. provision
F7.14 (PULSE min. provision)
-F7.13 (max. input pulse)
0.1K 10.0K ○
F7.17
PULSE max. provision corresponding
freq.
0.00-high limit frequency 0.01 Hz 50.00 Hz ○
F8-Motor and vector control parameter group
Function
code
Name Set range
Min.
unit
Factory
defaul
t
Modifi
-cation
F8.00 Control mode setting
0: V/F control
1: vector control
remark: for EDS1300 it can’t be 1
1 0 ×
F8.01 Motor rated voltage 1-480V 1V
Depend on
device type
×
F8.02 Motor rated current 0.1-999.9A 0.1A
Depend on
device type
×
F8.03 Motor rated frequency 1.00-400.00Hz 0.01 Hz
Depend on
device type
×
F8.04 Motor rated speed 1-9999r/min 1r/min
Depend on
device type
×
F8.05 Motor pole quantity 2-14 2
Depend on
device type
×
F8.06 Motor rated power 0.1-999.9KW 0.1
Depend on
device type
×
F8.07 Motor stator resistance 0.000-9.9999ohm 0.001 ohm
Depend on
device type
×
F8.08 Motor rotor resistance 0.000-9.9999ohm 0.001 ohm
Depend on
device type
×
F8.09 Motor stator leakage inductance 0.0-999.9mH 0.1 mH
Depend on
device type
×
F8.10 Motor rotor leakage inductance 0.0-999.9mH 0.1 mH
Depend on
device type
×
F8.11 Motor mutual inductance 0.0-999.9mH 0.1 mH
Depend on
device type
×
F8.12 Torque limit 50.0-200.0%(rated current) 0.1% 150.0% ×
F8.13 Speed loop proportion gain 0.000-6.000 0.001 0.700 ×
F8.14 Speed loop integral time constant 0.000-9.999 0.001 0.360 ×
F8.15 Motor stability coefficient 0-4 3 ×
F8.16 Filter time displayed instead freq. 0~999 1 6 ×
F8.17 Motor speed correction factor 0-9999% 0 100% ×
F9-Protection function parameter group
Function
code
Name Set range
Min.
unit
Factory
default
Modifi
-cation
F9.00
W
aiting time for
starting again when
p
ower off
0.0-20.0S (0 means do not enable this
function)
0.1S 0 ×
F9.01
Failure self-renew
times
0-10
0 shows no automatic reset function
Note:no automatic reset function when over
1 0 ×