www.enc.net.cn/en Tel/Fax:86-755-26984485/26985120 5 Function parameter schedule graph
52
15: inverter failure
16: swing frequency high&low limit restriction
17: interior counter reach final value
18: interior counter reach specified value
19: set runtime arrive
20: interior timing arrive
21: (Special for “one-drive-two” water supply)
OC1-variable frequency for the 1
st
pump
OC2-power source for the 1
st
pump
OC3- variable frequency for the 2
nd
pump
OC4-power source for the 2
nd
pump
22: reserved
23: reserved
24: reserved
F5.11
Open circuit
collector output
terminal OC2
output setting
Same as above 1 4 ×
F5.12
Open circuit
collector output
terminal OC3
output setting
Same as above 1 5 ×
F5.13
Open circuit
collector output
terminal OC4
output setting
Same as above 1 18 ×
F5.14
Frequency arriving
(FAR) detect range
0.00-50.00Hz 0.01Hz 5.00Hz ○
F5.15
FDT1 (frequency
level) electric level
0.00-high limit frequency 0.01Hz 10.00Hz ○
F5.16 FDT1 lag 0.00-50.00Hz 0.01Hz 1.00Hz ○
F5.17
Analog output
(AO1) selection
0: output frequency(0-high limit frequency)
1: set frequency(0-high limit frequency)
2: output current(0-2×rated current)
3: output voltage(0-1.2×load motor rated voltage)
4: bus-bar voltage(0-800V)
5: PID provision (0.00-10.00V)
6: PID feedback (0.00-10.00V)
7: reserved
8: reserved
9: reserved
1 0 ○
F5.18
Analog output
(AO1) gain
0.00-2.00 0.01 1.00 ○
F5.19
Analog output
(AO1) offset
0.00-10.00V 0.01 0.00 ○
F5.20
Analog output
(AO2) selection
Same as F5.17 1 0 ○
F5.21
Analog output
(AO2) gain
0.00-2.00 0.01 1.00 ○
F5.22
Analog output
(AO2) offset
0.00-10.00V 0.01 0.00 ○
F5.23
DO terminal
output function
selection
Same as F5.17 1 0 ○
F5.24
DO maximum
pulse output
frequency
0.1-20.0(max. 20KHz)Max. DO port output pulse
frequency corresponds to Max. value selected by
F5.23
0.1KHz 10.0 ○
F5.25 Set interior 0-9999 1 0 ○