www.enc.net.cn/en Tel/Fax:86-755-26984485/26985120 5 Function parameter schedule graph
51
20: closed-loop ineffective
21: PLC ineffective
22: simple PLC pause control
23: PLC stop status reset
24: frequency provision channel selection 1
25: frequency provision channel selection 2
26: frequency provision channel selection 3
27: frequency switched to CCI
28: command switched to terminal
29: run command channel selection 1
30: run command channel selection 2
31: run command channel selection 3
32: swing frequency jump-in
33: external interruption input
34: interior counter clearing end
35: interior counter triggering end
36: interior timer clearing end
37: interior timer triggering end
38: pulse frequency input(only effective forX7,X8)
39: reserved
40: reserved
41: reserved
42: reserved
F5.01
Input terminal X2
function selection
Same as above ×
F5.02
Input terminal X3
function selection
Same as above ×
F5.03
Input terminal X4
function selection
Same as above ×
F5.04
Input terminal X5
function selection
Same as above ×
F5.05
Input terminal X6
function selection
Same as above ×
F5.06
Input terminal X7
function selection
Same as above ×
F5.07
Input terminal X8
function selection
Same as above ×
F5.08
FWD/REV run
mode selection
0: 2-wire control mode 1
1: 2-wire control mode 2
2: 3-wire control mode 1
3: 3-wire control mode 2
1 0 ×
F5.09
UP/DOWN
velocity
0.01-99.99Hz/s 0.01Hz/s 1.00Hz/s ○
F5.10
Open circuit
collector output
terminal OC1
output setting
0: inverter running signal(RUN)
1: frequency arriving signal(FAR)
2: frequency level detect signal (FDT1)
3: reserved
4: overload warning signal (OL)
5: output frequency reach high limit(FHL)
6: output frequency reach low limit(FLL)
7: inverter under voltage blockage stop (LU)
8: stop for exterior failure(EXT)
9: inverter zero rotate speed running
10: PLC running
11: simple PLC segment running finished
12: PLC finish one cycle run
13: reserved
14: inverter ready to run (RDY)
1 0 ×