Service manual
www.enc.net.cn/en Tel/Fax:86-755-26984485/26985120 5 Function parameter schedule graph
49
12: analog input CCI/PID feedback
13: analog input YCI
14: exterior pulse inputs
F3.29
YCI run-in delay
time
0.0-999.9s 0.1 0.0 ○
PID feedback
signal loss
detection
0.0-999.9s 0.1 0.0 ○
F3.30
Failure relay TA,
TB,TC function
selection
0: inverter running(RUN)
1: frequency arriving signal(FAR)
2: frequency level detect signal (FDT1)
3: reserved
4: overload warning alarm signal (OL)
5: output frequency reach high limit(FHL)
6: output frequency reach low limit(FLL)
7: inverter under voltage blockage stop (LU)
8: external failure stop-running(EXT)
9: inverter zero speed running
10: PLC running
11: simple PLC section running finished
12: PLC finish a cycle running
13: reserved
14: inverter ready to run (RDY)
15: inverter failure
16: traverse high and low limit restriction
17: interior counter reach final value
18: interior counter reach specified value
19: set run time arriving
20: interior timing arriving
21: Multifunctional input terminal signal input
22: FWD running
23: REV running
24: reserved
15 ○
F3.31 Reserved
F4-Simple PLC function parameter group
Function
code
Name Set range
Min.
unit
Factory
default
Modifi
-cation
F4.00
Simple PLC
running setting
LED 1
st
bit:
0: no action
1: stop after single circulation
2: keep final value after single circulation
3: consecutive circulation
LED 2
nd
bit:
0: start from first step
1: continue to run from step freq. of interruption
moment
LED 3
rd
bit: PLC run time unit
0: second
1: minute
LED 4
th
b
it: PLC running state power off treatment
method
0:power off no memory
1:Running with memory when power off, renew
running after power on (terminal control
1 0000 ×