Service manual
www.enc.net.cn/en Tel/Fax:86-755-26984485/26985120 5 Function parameter schedule graph
47
value 3
F2.44
Muti-step freq. 15 Lower limit freq.-upper limit freq. 0.01Hz 80.00Hz ○
VF voltage value
3
F2.42-100.0% (rated voltage) 0.01% 80.00% ○
F2.45 Jumping freq. 1 0.00-400.00Hz 0.01Hz 0.00Hz ×
F2.46
Jumping freq. 1
range
0.00-30.00Hz 0.01Hz 0.00Hz ×
F2.47 reserved
F2.48 reserved
F2.49 reserved
F2.50 reserved
F2.51 Sett run time 0-65535 hours 1 0 ○
F2.52
Run time
accumulation
0-65535 hours 1 0 *
F2.53 reserved
F3-Closed-loop run function parameter group
Function
code
Name Set range
Min.
unit
Factory
default
Modifi
-cation
F3.00
Closed-loop run
control selection
0: closed-loop control ineffective
1: PID closed-loop control effective
2:
Specialized for constant water supply PID control
(F5.10~F5.13 must be set to 21)
1 0 ×
F3.01
Provision channel
selection
0: digital provision
1: VCI analog 0-10V voltage provision
2: CCI analog provision
3: keypad analog potentiometer provision
1 0 ○
F3.02
Feedback channel
selection
0: VCI analog input voltage 0-10V
1: CCI analog input
2: VCI+CCI
3: VCI-CCI
4: Min { VCI, CCI }
5: Max { VCI, CCI }
6: pulse feedback
1 0 ○
F3.03
Specified value
digital setting
0.000~9.999V(setF3.00=1,F3.21=9.999) 0.001 0.200 ○
Target pressure
value setting
0.000~F3.21Mpa(setF3.00=2) 0.001 0.200 ○
F3.04
Minimum
specified value
0.0-maximum specified value; percentage
relative to 10.00V
0.1(%) 0.000 ○
F3.05
Corresponding
feedback value
responding of
minimum
specified value
0.0-100.0(%) 0.1(%) 0.000 ○
F3.06
maximum
specified value
Minimum specified value
-100.0(%)
0.1(%) 100.0(%) ○
F3.07
Corresponding
feedback value
responding of
maximum
specified value
0.0-100.0(%) 0.1(%) 100.0(%) ○
F3.08 proportion gain Kp 0.000-9.999 0.001 0.150 ○
F3.09 Integral gain Ki 0.000-9.999 0.001 0.150 ○
F3.10 Differential gain 0.000-9.999 0.001 0.000 ○