Service manual
www.enc.net.cn/en Tel/Fax:86-755-26984485/26985120 5 Function parameter schedule graph
44
F2-Auxiliary run function parameter group
Function
code
Name Set range
Min.
unit
Factory
default
Modifi
-cation
F2.00
Analog filter time
constant
0.00-30.00s 0.01s 0.20s ○
F2.01
Forward reverse
run dead-section
time
0.0-3600.0s 0.1s 0.1s ○
F2.02
Automatic energy
save run
0: no action
1: action
1 0 ×
F2.03 AVR function
0: no action
1: action all the time
2: no action only during Dec
1 0 ×
F2.04
Slip frequency
compensation
0~150(%)0-no slip frequency compensation 1 0 ×
F2.05 Carrier wave freq.
0.5-15.0K
(Vary from different motor types; please see the
reference on chapter 6)
0.1K
depend
on
machine
type
×
F2.06 Jog run frequency 0.10-50.00Hz 0.01Hz 5.00Hz ○
F2.07 Jog Acce time 0.1-60.0s 0.1s 20.0s ○
F2.08 Jog Dece time 0.1-60.0s 0.1s 20.0s ○
F2.09
Frequency input
channel
combination
0: VCI+CCI
1: VCI-CCI
2: YCI+CCI
3: RS485+YCI
4: VCI+YCI
5: reserved
6: exterior pulse provision+CCI
7: exterior pulse provision-CCI
8: reserved
9: reserved
10: reserved
11: reserved
12: reserved
13: VCI, CCI any nonzero value effective, VCI
preferred
14: reserved
15: RS485+CCI
16: RS485-CCI
17: RS485+VCI
18: RS485-VCI
19: RS485+keypad potentiometer
20: RS485- keypad potentiometer
21: VCI+ keypad potentiometer
22: VCI- keypad potentiometer
23: CCI+ keypad potentiometer
24: CCI- keypad potentiometer
25: reserved
26: reserved
27: reserved
28: reserved
1 0 ×
F2.10
Main & sub
inverter
communication
frequency
provision
proportion
0-500(%) 1(%) 100(%) ○