5 Function parameter schedule graph
5.1 Symbol description
× ---- parameter can’t be changed in process of running
---- parameter can be changed in process of running
* ---- read-only parameter, unmodifiable
5.2 Function parameter schedule graph
F0Basic run function parameter group
Function
code
Name Set range
Min.
unit
Factory
default
Modifi
-cation
F0.00
Frequency input
channel selection
0: keypad analog potentiometer setting
1: keypad digital setting
2: terminal UP/DOWN adjust setting freq.
(stored after power off or stop)
3: serial port provision(not stored after power off)
4: VCI analog setting (VCI-GND)
5: CCI analog setting (CCI-GND)
6: YCI analog setting (YCI-GND)
7: terminal pulse (PULSE) setting
8: combination setting
9: terminal UP/DOWN adjust setting freq.
(not stored after power off)
10: serial port provision (stored after power off)
1 1
F0.01 Freq. digit setting Lower limit Freq.upper limit Freq. 0.01Hz 50.00Hz
F0.02
Run command
channel selection
0: keypad run control
1: terminal run command control
(keypad stop command ineffective)
2: terminal run command control
(keypad stop command effective)
3: serial port run command control
(keypad stop command ineffective)
4: serial port run command control
(keypad stop command effective)
1 0
F0.03
Run direction
setting
1
st
bit: 0, forward run; 1, reserved
2
nd
bit: 0, reverse run allowed
1, reverse run banned
3
rd
bit: REV/JOG key selection
0: as reverse run key
1: as jog key
1 100
F0.04
Acce/Dece mode
selection
0: linear Acce/Dece mode
1: S curve Acce/Dece mode
1 0 ×
F0.05
S curve start
time
10.0(%)50.0(%)(Acce/Dece time)
F0.05+F0.0690(%)
0.1(%) 20.0(%)
F0.06 S curve rising time
10.0(%)70.0(%)(Acce/Dece time)
F0.05+F0.0690(%)
0.1(%) 60.0(%)
F0.07
Acce/Dece time
unit
0: second
1: minute
1 0 ×
F0.08 Acce time 1 0.16000.0 0.1 20.0
F0.09 Dece time 1 0.16000.0 0.1 20.0
F0.10 Upper limit freq. Lower limit freq.400.00Hz 0.01Hz 50.00Hz ×